Generator

A 20 Ω, 50 mH load on 230 V at 50 Hz

computed by solving, not by drawing. The load draws 1636 W and 1285 var, an apparent power of 2080 VA at a power factor of 0.786. The reactive side is confirmed by a route that touches no impedance: 2ω times the energy stored in the inductor gives 1285 var. The cable carries 9.04 A and only 7.11 A of it does anything.
A 20 Ω, 50 mH load on 230 V at 50 Hzcomputed by solving, not by drawing. The load draws 1636 W and 1285 var, an apparent power of 2080 VA at a power factor of 0.786. The reactive side is confirmed by a route that touches no impedance: 2ω times the energy stored in the inductor gives 1285 var. The cable carries 9.04 A and only 7.11 A of it does anything.0500500100010001500150020002000real power (watts)reactive power (volt-amperes reactive)1636 W1285 var2080 VAreal power1636 Wreactive power1285 varapparent power2080 VApower factor0.7864angle38.15°line current9.04 A…doing work7.11 Athe load230 V20 Ω50 mHsolved, then checked — three routes to Qonly 0.79 of the current works

Drawn above at its default parameters, which is almost never how an essay calls it. A placement states the numbers that essay is arguing about, so the figure a reader meets is about that argument rather than about the generator — 98% of the placements on this site pass one, and the phase that raised that number from 12% found eight captions describing a figure the page was not showing.

At those defaults the edge it states is only 0.79 of the current works — the right-hand slot of the caption strip, which on this site is never used for anything else, and which is read back out of the drawing above rather than out of the code that wrote it. It belongs to Power, and the part that does no work, which is to say a change to it is a change to lib/figures/power.js. It takes a slider on load inductance (henries) with 7 settings, and every one of them has passed the same assertions as the frame above — a figure whose circuit stops doing what its caption says at any setting stops the build.

Called by 6 essays

which is the blast radius of changing it

The current that does no work

A solved network has been reporting its own real power on every page of this collection, as the second of the two checks each answer passes before it is drawn. What that check discards is the imaginary half — the power that flows out to a reactance and back again, does nothing, and is still carried by the cable, still heats the transformer, and is still on the bill.

Power, and the part that does no work

The capacitor that was right once

Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.

Power, and the part that does no work

The load that takes the most

A load equal to the source resistance takes more power than any other, and it does so at exactly fifty per cent efficiency — the source burns as much as the load receives. Ninety per cent efficiency needs a load nine times the source and delivers 36% of what was available, and a load half the source resistance delivers exactly as much as one twice it.

Power, and the part that does no work

The far end that rises

Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.

Power, and the part that does no work

The reactance cancelled, and the resonance it buys

Putting a capacitor in series with a feeder cancels part of its reactance and the far end falls less: five per cent of regulation becomes four and a quarter at a quarter compensation and 2.7 per cent at seventy per cent. What comes with it is a series resonance that was not there before, at the line frequency times the root of the fraction cancelled — so a quarter compensation resonates at exactly half the line frequency and a ninth at exactly a third. The line's own inductance is not in that answer and neither is the voltage.

Power, and the part that does no work

The energy a unity power factor doubles

Reactive power was computed three ways on this site and the agreement was called a verification. Two of the three are one theorem written twice and cannot disagree about anything; only the third is independent, and what it computes is a difference. Correcting a 20 Ω, 50 mH load to a power factor of 1.000000 takes its reactive power from 1,285 var to nothing and takes the energy stored in the installation from 2,044.9 mJ to 4,089.7 mJ — exactly twice, at every load and every frequency.

Power, and the part that does no work

Every generator