Inrush — the series
-
The first cycle, which no steady state contains
Every number this field computes about a rectifier — the ripple, the crest factor, the conduction angle, the power factor — is read from the settled state, and the march that produces them starts from an empty capacitor and throws the first cycle away. That first conduction carries 32.4 amperes against a repetitive peak of 1.23, it is 26 times larger than anything the circuit ever does again, and how large it is depends on when somebody's hand closed the switch.
-
The inductance that limits, and lifts
Adding winding resistance to a rectifier limits the first peak and does not reduce the energy at all — the essay below measured ∫i²dt as two per cent apart over a factor of four in the resistance. Adding leakage inductance does both: it divides the peak by seven and the energy by five, and dissipates nothing to do it. What it buys instead is a rectifier whose output sits 29 per cent above the peak of its own supply, permanently, which every steady-state expression in this field says cannot happen.
-
The instant a transformer is worst at
A capacitor-input rectifier draws its worst inrush when it is switched on at the peak of the mains. A transformer's own magnetising branch is the other way round: switched on at the voltage zero, a 230 V primary worked at 1.4 T draws 87.6 A in its first half-cycle, 791 times its settled magnetising current, and at the voltage peak it draws nothing extra at all. The core's flux has to start from zero, the voltage does not, and how close the working flux sits to half of saturation decides the size.
-
The harmonic that names an inrush
A transformer's differential relay sees an inrush as current going in and nothing coming out, which is what an internal fault looks like, and it tells them apart by the second harmonic. Marched cycle by cycle, an inrush starts at 79% second harmonic and stays above the usual 15% restraint for thirty cycles — long after its current has fallen from 88 A to 205 mA, because the current unwinds in a few cycles and the flux offset under it takes seconds. A fault's offset is a smooth exponential and peaks at 14.6% only when X/R is as low as three.