  1. One capacitor of 77.3 µF, against every load it was not sized for. computed by solving, not by drawing. Sized from the 20 Ω load, the capacitor takes the power factor to 1.000000 there and leaves 0.0e+0 var of 1636 VA. At 178 Ω the same installation sits at 0.23 leading. The correction is exact at one point on this axis and nowhere else on it.

    The capacitor that was right once

    Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.