Series

Power factor correction — the series

2 essays on one idea, from the one that introduces it to the one that assumes the rest.
  1. One capacitor of 77.3 µF, against every load it was not sized for. computed by solving, not by drawing. Sized from the 20 Ω load, the capacitor takes the power factor to 1.000000 there and leaves 0.0e+0 var of 1636 VA. At 178 Ω the same installation sits at 0.23 leading. The correction is exact at one point on this axis and nowhere else on it.

    The capacitor that was right once

    Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.

    part 2 · power
  2. A 640 kvar bank on a 16 MVA 400 V bus: alone its resonance with the supply is at h = 5.00, and with a 7% reactor in series at 3.01, with the bank's own null at 3.78 between that and everything above it. computed by solving, not by drawing: the impedance per phase at a 400 V bus, with a short-circuit level of 16 MVA and a 640 kvar correction bank, against harmonic order, in closed form and at the fifth by a netlist. The bank alone (dashed) resonates with the supply at h = 5.00, where the bus impedance peaks. With a reactor of 7% of the capacitor's fundamental reactance in series (solid), the bank's own series resonance is at h = 1/√0.07 = 3.78, a deep null, and the parallel peak has moved down to h = 3.01. Above the null the bank is an inductor, in parallel with the supply's inductance, so there is nothing for any higher harmonic to resonate with.

    The reactor that keeps a bank out of it

    A correction bank on a stiff bus resonates with the supply at a harmonic set by the two sizes, and at 640 kvar on 16 MVA that harmonic is the fifth, which it multiplies by 34. A reactor of 7 per cent of the capacitor's reactance in series puts a null at h = 3.78, and above that null the bank is an inductor, in parallel with another inductor, with nothing left to resonate. So the fifth is never raised at any size of bank. It was not free. The capacitor now stands 7.5 per cent above the bus, the resonance has gone below the null and can land on the third, 22.7 times at 654 kvar, and the number that looks like a detail, 7 rather than the 4 that would tune the bank to the fifth, is what keeps an ageing bank on the right side of its null.

    part 3 · power

All series