Reactive power — the series
-
The current that does no work
A solved network has been reporting its own real power on every page of this collection, as the second of the two checks each answer passes before it is drawn. What that check discards is the imaginary half — the power that flows out to a reactance and back again, does nothing, and is still carried by the cable, still heats the transformer, and is still on the bill.
-
The energy a unity power factor doubles
Reactive power can be computed three ways, and their agreement is easily called a verification. Two of the three are one theorem written twice and cannot disagree about anything; only the third is independent, and what it computes is a difference. Correcting a 20 Ω, 50 mH load to a power factor of 1.000000 takes its reactive power from 1,285 var to nothing and takes the energy stored in the installation from 2,044.9 mJ to 4,089.7 mJ — exactly twice, at every load and every frequency.
-
The capacitor two-thirds of the way out
A feeder's reactive current costs loss in every section it passes through, and on a feeder whose load is spread along its length that current is largest at the substation and falls to nothing at the far end. Correcting it at the substation removes no loss at all. One phase of an 11 kV feeder carrying 2 MW at 0.8 lagging over ten kilometres loses 16.8 kW, of which 5.66 kW is the reactive current's; the best single capacitor is about two-thirds of the load's reactive power placed about two-thirds of the way out, and it removes 87.6% of that share — against the eight-ninths the textbook rule gives for an idealised line. Two capacitors at 2/5 and 4/5 remove 95.6%. The same capacitor left in at light load costs more than it saves below half load, and the rule for a continuous load is a statement about many taps.