Generator

The neutral of a three-phase supply with one phase 30% off

computed by solving, not by drawing. Balanced, the three line currents sum to 4.6e-16 of one of them and the neutral carries nothing. With one phase 30% heavier the neutral carries 2.65 A against a line current of 11.50 A. The neutral reaches a tenth of a line current at 11.1% imbalance.
The neutral of a three-phase supply with one phase 30% offcomputed by solving, not by drawing. Balanced, the three line currents sum to 4.6e-16 of one of them and the neutral carries nothing. With one phase 30% heavier the neutral carries 2.65 A against a line current of 11.50 A. The neutral reaches a tenth of a line current at 11.1% imbalance.the three line currents, and their sum2.65 A in the neutral00.2000.40000.2000.4000.6000.8001imbalance in one phaseneutral current ÷ line currenta tenth of a line current11.1%solved, then checked — neutral by two routesa tenth of a line at 11.1% imbalance

Drawn above at its default parameters, which is almost never how an essay calls it. A placement states the numbers that essay is arguing about, so the figure a reader meets is about that argument rather than about the generator — 98% of the placements on this site pass one, and the phase that raised that number from 12% found eight captions describing a figure the page was not showing.

At those defaults the edge it states is a tenth of a line at 11.1% imbalance — the right-hand slot of the caption strip, which on this site is never used for anything else, and which is read back out of the drawing above rather than out of the code that wrote it. It belongs to Power, and the part that does no work, which is to say a change to it is a change to lib/figures/power.js. It takes a slider on extra load on one phase with 7 settings, and every one of them has passed the same assertions as the frame above — a figure whose circuit stops doing what its caption says at any setting stops the build.

Called by 3 essays

which is the blast radius of changing it

Three phases, and the wire that carries nothing

Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.

Power, and the part that does no work

The neutral that carries more than a line

Three balanced loads draw currents summing to 5.3 × 10⁻¹⁵ amperes in the neutral. That is a theorem about sinusoids, and it uses nothing except that each current is a single frequency. A harmonic of order three is shifted by 360° between phases, which is no shift at all — so the third harmonics add, and for any conduction angle narrow enough that the pulse trains stay disjoint the neutral carries exactly √3 times a line current.

Power, and the part that does no work

The half the neutral does not carry

A star load unbalanced in one phase produces two things, not one. The neutral carries three times the zero-sequence current, which is the half this collection has read; the other half is a negative-sequence set of exactly the same size, rotating backwards, that the neutral never sees. With 0.5 Ω of line in front of 20 Ω loads, losing a phase entirely puts 50.00 per cent negative sequence in the current and 0.8265 per cent in the voltage a switchboard meter reads.

Power, and the part that does no work

Every generator