Power, and the part that does no work

Three phases, and the wire that carries nothing

Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.

Until this page every source on this site has had a real value. That was never stated as a restriction because nothing needed it lifted: one source in a network sets the reference angle, and every phase in the answer is measured from it. Three sources is the first circuit where the phases between the sources are the subject, and a real number cannot carry one.

So the assembler was extended. A source’s value may now be a complex number, its imaginary half is carried in a second source vector beside the real one, and everything downstream of the solve is unchanged. The documentation for V has said “value is its phasor” since the first commit; this is the first circuit that took it at its word.

The neutral of a three-phase supply with one phase 30% offcomputed by solving, not by drawing. Balanced, the three line currents sum to 4.6e-16 of one of them and the neutral carries nothing. With one phase 30% heavier the neutral carries 2.65 A against a line current of 11.50 A. The neutral reaches a tenth of a line current at 11.1% imbalance.the three line currents, and their sum2.65 A in the neutral00.2000.40000.2000.4000.6000.8001imbalance in one phaseneutral current ÷ line currenta tenth of a line current11.1%solved, then checked — neutral by two routesa tenth of a line at 11.1% imbalance
Fig. 1 Three 230 V sources at 0°, −120° and +120°, feeding three loads through a neutral of one milliohm. On the left the three line currents are drawn as arrows, with their sum; on the right the neutral current against the imbalance in one phase. Balanced, the sum is 5×10⁻¹⁵ of a line current. The slider is the extra load on one phase, and the marked edge is where the neutral reaches a tenth of a line current.

Why the sum is zero

Three unit phasors at 0°, −120° and +120° sum to zero, and the reason is that they are the three cube roots of one. Their sum is the coefficient of the second-highest term in z³ − 1 = 0, which is absent, so the sum is exactly zero — an algebraic fact rather than a numerical coincidence.

Feed three identical impedances from them and each current is the same complex number divided by the same impedance, so the currents are also three phasors a third of a cycle apart and they sum to zero too. The neutral wire is therefore carrying nothing, and the solved network agrees: the measured sum comes out at 5.3×10⁻¹⁵ of a line current, which is the arithmetic’s own floor.

That is the entire economic argument for three-phase distribution. Three wires deliver three loads’ worth of power, and the fourth wire — the one that would be needed to return the current in a single-phase system — can be thin or, in some arrangements, absent.

Three element voltages closing on one source, at 1.59 kHzSolved at 1.59 kHz, which is 1.00× the frequency at which the two reactances cancel. The three phasors add head to tail to the 1 V source exactly; their magnitudes sum to 5.26 V, which is not the same statement.realimaginaryacross Racross Lacross Cthe source, 1 Vmagnitudes|v_R| = 1.000 V|v_L| = 2.128 V|v_C| = 2.128 Vsum 5.255 Vvector sum 1.000 Vsolved, then checked — one solve at 1.59 kHzsteady state only: 3 cycles to settle
Fig. 2 The construction from the frequency field, which is the same one at work here. Phasors add by direction and not by magnitude, which is why three currents of 11.5 A each can sum to nothing. The picture in the hero figure is this one with three arrows at a hundred and twenty degrees, and the sum is at the centre.

The factor of √3, which is a geometry rather than a convention

Two voltages are available in a star-connected supply and the ratio between them is the one number in this subject most often quoted and least often derived.

The voltage from any line to the star point is the source’s own, 230 V here. The voltage between two lines is the difference of two phasors a third of a cycle apart, and the difference of two unit phasors 120° apart has magnitude 2 sin 60° = √3. So the line-to-line voltage is 230 × √3 = 398 V, which is the 400 V that appears on every nameplate in Europe.

Nothing about that is a convention. It is the length of the third side of a triangle whose other two sides are equal and meet at 120°, and it is the same construction three voltages that close uses to show that a series circuit’s element voltages can each exceed the source. The arithmetic is identical; only the drawing is rotated.

The consequence is that a three-phase supply offers two voltages from the same four wires, and a load can be connected between a line and the neutral or between two lines. A load connected between two lines draws no current in the neutral at all — it has no connection to it — which is one reason larger equipment is usually wired that way, and one reason an installation’s neutral loading is decided by its small loads rather than its large ones.

A network solved, and checked: a bridge, which no series-parallel reduction reachesNode potentials from modified nodal analysis. The branch currents are then recomputed from each element's own law and summed at every node; the residual is 2.7e-16 of the largest current in the circuit, which is floating-point rounding and nothing else.a bridge, which no series-parallel reduction reachesnode a7.5566 Vnode b4.7993 Vcurrent law, rebuilt from the element laws2.71e-16 of the largest branch currentpower delivered against power dissipated4.33e-16 apart · 48.07 mWsolved, then checked — 6 elementsa linear network has no edge: this one is exact
Fig. 3 A network solved and checked: the branch currents rebuilt from each element’s own law and summed at every node, and the energy counted twice. Everything on this page runs through that check, which is what makes a neutral current of 5×10⁻¹⁵ a statement about the circuit rather than about the arithmetic. A solver that silently mis-stamped one of the three sources would produce a plausible star of three arrows and would fail here.

The second route

A claim that a wire carries nothing is a claim worth checking by a method that does not look at the wire, and one is available.

Any three phasors can be decomposed into three symmetrical components: a positive-sequence set rotating one way, a negative-sequence set rotating the other, and a zero-sequence set in which all three are identical. The zero-sequence component is the average of the three, and the neutral carries exactly three times it.

The routine that computes it takes the three line currents and produces the average with two complex rotations. Nothing in it touches the neutral branch, its resistance, or the solve that produced it beyond reading the three currents out. It agrees with the neutral current from the network to a part in 10⁹ at every imbalance on the slider.

For the balanced case both routes report zero, which is not a strong test — two routes agreeing on zero is easy. For the unbalanced case at thirty per cent they report the same 2.654 A, and that is a test: two different constructions of the same quantity, sharing only the solve.

The decomposition is worth a second look because it also says what kind of imbalance is present, which the neutral current on its own does not. A load imbalance that is purely a difference in magnitude produces zero- and negative-sequence components together; a set of currents that are equal in magnitude but wrongly spaced in angle produces a negative-sequence component and no zero-sequence one at all, and puts nothing in the neutral while still heating a motor connected between the lines. The neutral current is therefore a partial indicator: it detects one of the two ways a supply can be unbalanced and is silent about the other. A three-phase motor fed from a supply with a two per cent negative-sequence component runs measurably hotter for reasons that no neutral measurement can see, because the motor’s rotor is being driven backwards by a small counter-rotating field.

How quickly it stops being zero

The interesting question is not whether the sum is zero when everything matches — it is, exactly — but how much mismatch it takes for the neutral to carry something that matters.

Bisecting on the solved network with one phase’s resistance scaled by 1 + x gives the answer: at x = 0.111, the neutral carries a tenth of a line current. Eleven per cent.

That number deserves a moment. Eleven per cent is not a fault condition. It is the ordinary difference between three circuits in an office with different numbers of things plugged into them, or three phases of a lighting installation where one corridor has more fittings than another. Nothing has gone wrong, nobody has made a mistake, and the neutral is carrying ten per cent of a line current.

The neutral of a three-phase supply with one phase 5% offcomputed by solving, not by drawing. Balanced, the three line currents sum to 4.6e-16 of one of them and the neutral carries nothing. With one phase 5% heavier the neutral carries 0.55 A against a line current of 11.50 A. The neutral reaches a tenth of a line current at 11.1% imbalance.the three line currents, and their sum0.55 A in the neutral00.2000.40000.2000.4000.6000.8001imbalance in one phaseneutral current ÷ line currenta tenth of a line current11.1%solved, then checked — neutral by two routesa tenth of a line at 11.1% imbalance
Fig. 4 The same supply at five per cent imbalance. The three arrows are barely distinguishable in length and the sum is visible but small. Between this figure and the one above lies the whole practical question: the neutral current is roughly proportional to the imbalance, so nothing dramatic happens at any particular point and there is no threshold to design against.

Proportionality is what makes this awkward rather than dangerous. There is no cliff. A neutral sized at half a line conductor is fine up to roughly fifty per cent imbalance and the installation gives no warning as it approaches. The failure mode of an undersized neutral is a slow one — heat, then a loose connection, then a connection that arcs — and it is not detected by anything that monitors the three phases.

It is worth being explicit about what the eleven per cent is a property of, because the number moves. The bisection scales one phase’s resistance while holding the other two, so it describes a very particular kind of imbalance: one phase heavier, two equal. Imbalance distributed differently gives a different answer — one phase lighter and two equal is not the mirror image, because resistance and current are reciprocally related and a ten per cent lighter load does not draw ten per cent less current — and two phases displaced in opposite directions can produce a much larger neutral current for the same total departure from balance.

What survives all of those variations is the order of magnitude, and that is the useful part: the neutral current is roughly the arithmetic imbalance rather than something smaller. There is no averaging, no partial cancellation, no factor that makes a ten per cent difference produce a one per cent current. The three phasors sum to zero exactly when they are equal and to something of the order of their difference when they are not.

A worked case makes the scale concrete. Three twenty-ohm loads on 230 V draw 11.500 A each. Make one of them thirty per cent heavier — that is, raise its resistance by thirty per cent, so it draws 8.846 A instead — and the neutral carries 2.654 A, which is twenty-three per cent of a line current. The imbalance in the current was 2.654 A and the neutral carries 2.654 A: the whole of it, arriving in the conductor that was sized on the assumption that imbalance was the exception.

The harmonics that do not cancel

There is a second mechanism, and it does not obey the proportionality above at all.

The cancellation argument rests on three phasors being a third of a cycle apart. Shift each of them by a third of a cycle and the set is unchanged, which is the symmetry that makes the sum vanish. Now consider the third harmonic of each phase’s current. Shifting the fundamental by a third of a cycle shifts the third harmonic by a whole cycle — that is, by nothing at all. The three third harmonics are therefore in phase with one another, and instead of cancelling in the neutral they add.

The same is true of the ninth, the fifteenth, and every odd multiple of three, which is why they are collected under the name triplen.

A load conducting for 60° either side of each peakcomputed by solving, not by drawing over 1024 samples of one cycle. The current's fundamental is exactly in phase with the voltage, so the displacement factor — the cos φ a phasor calculation returns — is 1.000000. The true power factor is 0.7803, and the difference is the distortion factor 0.7803: the same 100 W drawn as 0.558 A rather than the 0.435 A a sinusoid would need.supply voltagecurrent drawnone cycle of the mainsharmonics of the current, against the fundamental11.000230.665450.198670.144890.222displacement (cos φ): 1.000000distortion: 0.7803true power factor: 0.7803solved, then checked — Parseval on the currentcos φ says 1.000, the meter says 0.780
Fig. 5 The current a load draws when it conducts only near the peaks of the supply, and its harmonic content. The third harmonic here is a substantial fraction of the fundamental, and in a three-phase installation every phase’s third harmonic arrives at the neutral in step with the other two. Three loads that are perfectly balanced at the fundamental are not balanced at all at the third.

The consequence is one of the few genuinely counter-intuitive results in distribution: a perfectly balanced three-phase installation of non-linear loads can have a neutral current larger than any of its line currents. Not a fraction of one — larger. The fundamental cancels completely, the triplen harmonics add to three times their per-phase value, and if the third harmonic is a third of the fundamental the neutral carries as much as a line does.

None of that is visible to a measurement of the fundamental, or to a power factor computed as cos φ, or to any calculation that represents a current as a single phasor. It requires the current’s shape, which is the quantity the capacitor that was right once also turns on.

What the milliohm is doing there

One detail of the netlist is a deliberate choice and worth defending, because it looks like a fudge.

The neutral is a one-milliohm resistor rather than a wire. That is not an approximation to a connection; it is the honest way to say “connected”, because a short circuit between two nodes is a constraint and not an element, and stamping it as an admittance of infinity is how a matrix acquires a row of nonsense. The assembler refuses a resistance of zero by name for exactly that reason.

A milliohm is four orders below the smallest load on the page, so it changes no digit that is printed. What it buys is that the figure which removes the neutral does so by making that resistance large rather than by deleting a line — the same circuit at two parameter values, with the same solver and the same checks, rather than two circuits that have to be trusted to correspond. The distinction matters whenever a limiting case is being drawn: a limit approached through a parameter can be checked at every point along the way, and a limit reached by editing the netlist cannot.

The star point, and what happens without a neutral

A 20 Ω, 20 mH load on 230 V at 50 Hzcomputed by solving, not by drawing. The load draws 2407 W and 756 var, an apparent power of 2523 VA at a power factor of 0.954. The reactive side is confirmed by a route that touches no impedance: 2ω times the energy stored in the inductor gives 756 var. The cable carries 10.97 A and only 10.47 A of it does anything.01000100020002000real power (watts)reactive power (volt-amperes reactive)2407 W756 var2523 VAreal power2407 Wreactive power756 varapparent power2523 VApower factor0.9540angle17.44°line current10.97 A…doing work10.47 Athe load230 V20 Ω20 mHsolved, then checked — three routes to Qonly 0.95 of the current works
Fig. 6 One phase’s power triangle. Three of these, and the total real power delivered by a balanced three-phase supply is exactly three times one of them — while the instantaneous power, unlike the single-phase case, does not pulse at twice the line frequency but is constant. That constancy is why three-phase motors do not vibrate at 100 Hz and single-phase ones do.

Removing the neutral is modelled here by making its resistance large rather than by deleting a wire, which keeps it the same circuit at a different parameter value and keeps the solver’s refusals meaningful — a network with a node that has no path to ground is refused by name rather than returned as a large plausible number.

With the neutral gone and the load balanced, nothing changes: the star point sits at zero anyway, so a wire carrying no current can be removed with no effect. With the neutral gone and the load unbalanced, the star point moves, and it moves in the direction that makes things worse: the lightly loaded phase sees a higher voltage and the heavily loaded one a lower voltage. A three-phase supply without a neutral does not merely fail to correct imbalance; it converts a current imbalance into a voltage imbalance, which is why the neutral is present in every distribution arrangement that feeds single-phase loads.

The efficiency argument, restated

The load that takes the most power, and the load that wastes the leastcomputed by solving, not by drawing at 71 load values. The power into the load peaks at a ratio of 1.000000, where the efficiency is exactly 0.500000 — the source dissipates as much as the load receives. Ninety per cent efficiency needs a ratio of 9.7 and delivers 34% of the available power.00.250.500.751100m110load resistance ÷ source resistancefraction of the maximumpower into the loadefficiencymatched: most power, half of it wasted90% efficient at 9.7×solved, then checked — the maximum searched, not quotedthe matched load wastes exactly half
Fig. 7 Power into a load and efficiency out of a source, from the field’s first essay. Distribution sits at the extreme right of this axis: the source impedance is made as small as possible and the load is many times it, so the efficiency is near one and the power transferred is far from its maximum. The maximum power theorem is exactly the wrong objective here, and the reason is on the curve.

That figure is worth revisiting in this context because it explains why three-phase distribution is shaped the way it is. A distribution system is not trying to extract the most power from a source; it is trying to lose the least in the wires. Every design decision follows: high voltage, so the current is small; three phases, so the return current is nothing; a low source impedance, so the voltage does not sag.

The neutral is where that logic has an exception, and this essay is about the size of it. Three phases make the return current zero under an assumption — balance — that holds well enough to be worth building on and not well enough to be built on carelessly. Eleven per cent of imbalance, or one rectifier per phase, is enough to make the wire that carries nothing carry something.