Generator

The load that takes the most power, and the load that wastes the least

computed by solving, not by drawing at 71 load values. The power into the load peaks at a ratio of 1.000000, which is the magnitude of the source impedance to six figures, and the efficiency there is 0.500000 — the source dissipates as much as the load receives. Ninety per cent efficiency needs a ratio of 9.7 and delivers 34% of the available power.
The load that takes the most power, and the load that wastes the leastcomputed by solving, not by drawing at 71 load values. The power into the load peaks at a ratio of 1.000000, which is the magnitude of the source impedance to six figures, and the efficiency there is 0.500000 — the source dissipates as much as the load receives. Ninety per cent efficiency needs a ratio of 9.7 and delivers 34% of the available power.00.250.500.751100m110load resistance ÷ source resistancefraction of what a resistive source could givepower into the loadefficiencymatched: most power, half of it wasted90% efficient at 9.7×solved, then checked — the maximum searched, not quotedthe matched load wastes exactly half

Drawn above at its default parameters, which is almost never how an essay calls it. A placement states the numbers that essay is arguing about, so the figure a reader meets is about that argument rather than about the generator — 98% of the placements on this site pass one, and the phase that raised that number from 12% found eight captions describing a figure the page was not showing.

At those defaults the edge it states is the matched load wastes exactly half — the right-hand slot of the caption strip, which on this site is never used for anything else, and which is read back out of the drawing above rather than out of the code that wrote it. It belongs to Power, and the part that does no work, which is to say a change to it is a change to lib/figures/power.js. It takes a slider on source reactance (ohms) with 5 settings, and every one of them has passed the same assertions as the frame above — a figure whose circuit stops doing what its caption says at any setting stops the build.

Called by 6 essays

which is the blast radius of changing it

The load that takes the most

A load equal to the source resistance takes more power than any other, and it does so at exactly fifty per cent efficiency — the source burns as much as the load receives. Ninety per cent efficiency needs a load nine times the source and delivers 36% of what was available, and a load half the source resistance delivers exactly as much as one twice it.

Power, and the part that does no work

The far end that rises

Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.

Power, and the part that does no work

The load that has two voltages or none

A load that takes a fixed power takes more current as its voltage falls, and on a line with impedance in it every power below a limit is delivered at two voltages and every power above it at none. The limit sits at the load the maximum-power theorem describes, half the source voltage on a resistive line. On fifty ohms and a hundred of reactance a load leading by sixty degrees reaches that limit with its far end at 1.055 of the source, and at nine tenths of it reads 1.172 — so a far end that reads high is not a far end with margin. On a direct-current bus the lower of the two voltages is not a state at all: one per cent below it the bus runs down to nothing in 3.48 milliseconds.

Power, and the part that does no work

The load that may be complex

Freed of the constraint that it be a resistance, the best load is the source's conjugate — found here by a two-dimensional search on the solved network rather than assumed — and it takes the available power at exactly fifty per cent efficiency whatever the source's reactance. A load that may only be a resistance takes 2/(1 + √(1+x²)) of that, and at a source reactance of twice its resistance that is exactly the golden ratio less one, 0.618034. The resistor-only load is also the MORE efficient of the two, rising towards one while the conjugate sits at a half for ever.

Power, and the part that does no work

The headroom that is the line's own charge

A line of 50 + j100 ohms delivers at most 0.6180 of a matched resistive line's power to a unity-power-factor load, with 0.5878 of the source voltage left. Give the line its own shunt capacitance — a π, half at each end, B|Z| = 0.4 in all — and the nose moves to 0.7025 at 0.6895: 13.7 per cent more power and 17.3 per cent more voltage. It is headroom, but not the headroom the far end advertises, which with no load rises 21.1 per cent. The capacitance turns the source and line into a Thevenin equivalent with more voltage behind more impedance, and it moves a voltage threshold's meaning in opposite directions depending on whether it is referred to the source or to the unloaded far end.

Power, and the part that does no work

The regulator that pushes past the nose

A regulator that raises a ratio whenever its load's voltage is low is a stabiliser only while raising the ratio raises the voltage, and on a line that stops being true at exactly the nose: the load's voltage, n·V₀ times the load resistance over n²R plus that resistance, peaks at a turns ratio of the square root of the load over the line and falls beyond it. Ask the load for 90 per cent of the nose power and the regulator settles at n = 1.519 — unless it starts above n = 2.925, where the same setpoint is met on the wrong side of the peak, and then it collapses the voltage. Ask for 101 per cent and the voltage climbs to 9.950 volts, the most the line allows, and is below half its setpoint 256 seconds later. Near the nose the collapse takes a time that grows as the inverse square root of the excess: 2,521 seconds at a hundredth of a per cent.

Power, and the part that does no work

Every generator