Power, and the part that does no work

The regulator that pushes past the nose

A regulator that raises a ratio whenever its load's voltage is low is a stabiliser only while raising the ratio raises the voltage, and on a line that stops being true at exactly the nose: the load's voltage, n·V₀ times the load resistance over n²R plus that resistance, peaks at a turns ratio of the square root of the load over the line and falls beyond it. Ask the load for 90 per cent of the nose power and the regulator settles at n = 1.519 — unless it starts above n = 2.925, where the same setpoint is met on the wrong side of the peak, and then it collapses the voltage. Ask for 101 per cent and the voltage climbs to 9.950 volts, the most the line allows, and is below half its setpoint 256 seconds later. Near the nose the collapse takes a time that grows as the inverse square root of the excess: 2,521 seconds at a hundredth of a per cent.

Assumes: The far end that rises · A bias point is a solution, not a choice

The load that has two voltages or none marched a direct-current bus into a load that takes a fixed power and found that the lower of its two operating points is not a state. A load that draws more current as its voltage falls has an incremental resistance of V2/P-V^2/P; below the lower point that negative resistance beats the bus’s own, and one per cent below it the bus runs down to nothing in 3.48 milliseconds.

Real loads are rarely constant power on the scale of milliseconds. A heater, a lamp or a resistive process is a resistance: pull its voltage down and it takes less power. It becomes a constant-power load only on a longer scale, through something that restores its voltage — and on a supply network that something is very often a regulator. A transformer with a tap changer, or an automatic voltage regulator, watches the voltage at the load and raises its ratio when the voltage sags. With a resistive load behind it the regulator restores the load’s power along with its voltage, and on the timescale of the regulator the combination is a constant-power load.

The same essay named the question that follows. Above the nose, raising the voltage the load sees is benign. Past it, raising it makes the line deliver less, and the regulator keeps pushing. This essay marches a regulator against a line and finds how, when and how fast the correction becomes the collapse.

The nose itself has been measured on this subject from several directions, and each is a piece of what the regulator runs into. The load that takes the most found the resistive load that draws a line’s most power, which is the ratio at the peak here; the load that may be complex freed its reactance and found the conjugate; the far end that rises found a far end reading above its source; and the headroom that is the line’s own charge moved the nose with the line’s capacitance. A load that restores its power turns each of those static limits into a dynamic one, and the incremental resistance of V2/P-V^2/P that makes it do so is a relative of the negative resistance the resistance that is below zero found in a follower — a device whose current rises as its voltage falls, placed where a positive resistance was expected.

The bus that could not hold its lower point

A load taking 90% of a bus's most power has two operating points, and only one of them holds. A 10 V direct-current bus of 1 Ω feeding a load that takes a fixed 22.50 W through a 1 mF capacitor, marched with a fourth-order rule from one per cent either side of each operating point. The operating points are 6.5811 V and 3.4189 V, the two roots of V² − V₀V + PR. From either side of the upper one the bus returns to it. From one per cent above the lower one it climbs to the upper, and from one per cent below it runs down to nothing in 3.48 ms, because a load that takes more current as its voltage falls has an incremental resistance of −V²/P, and below the lower point that negative resistance wins against the bus's own.
Fig. 1 A 10 V bus of 1 Ω feeding a load that takes a fixed 22.5 W through a 1 mF capacitor, marched from one per cent either side of each operating point. The points are 6.5811 V and 3.4189 V. From either side of the upper one the bus returns; from one per cent below the lower one it runs down to nothing in 3.48 ms.

The earlier result is the starting point and the contrast. There the constant-power behaviour was built into the load, and the instability lived in the bus’s own dynamics, with a time constant set by a capacitor and a resistance. Here the load is an ordinary resistance and the constant-power behaviour is manufactured by a control loop, so the instability lives in the regulator, and its timescale is the regulator’s.

What the ratio buys

The circuit is as plain as the argument allows. A ten-volt source behind one ohm of line feeds a load resistance through an ideal transformer of ratio nn — or anything that multiplies voltage and divides current. Seen from the line, the load is RL/n2R_L/n^2, and the voltage at the load is

V=nV0RLn2R+RL.V = \frac{n V_0 R_L}{n^2 R + R_L}.

That expression rises with nn, reaches a maximum, and falls. The maximum is at n=RL/Rn = \sqrt{R_L/R}, where the load reflected through the ratio equals the line’s resistance, and the voltage there is V0RL/R/2V_0\sqrt{R_L/R}/2: the ratio that gives the load the most voltage is the ratio that makes the line deliver its most power, V02/4RV_0^2/4R, which is 25 watts here. Past that ratio, further raising makes the reflected load smaller than the line, the line delivers less power, and the load’s voltage falls.

The load's voltage against the ratio peaks at √(Rₗ/R): below the nose power the setpoint is met twice, at 1.519 and 2.925. Solved at each ratio. A 10 V source behind 1 Ω feeds a load through an ideal ratio n; the load's resistance takes 90%, 100% and 110% of the line's most power at 10 V. The load's voltage is n·V₀·Rₗ/(n²R + Rₗ), which peaks at n = √(Rₗ/R). For the 90% load the peak is 10.5409 V at n = 2.1082 and the setpoint is met at n = 1.5195, where raising the ratio raises the voltage, and at n = 2.9250, where raising it lowers the voltage — the two multiply to Rₗ/R. For the 100% load the peak is the setpoint exactly, at n = 2.0000; for the 110% load it is 9.5346 V, and the setpoint is met nowhere. A regulator that raises the ratio whenever the voltage is below the setpoint is stabilising left of each peak and destabilising right of it.
Fig. 2 The load’s voltage against the ratio, for load resistances that take 90%, 100% and 110% of the line’s most power at 10 V. For the 90% load the voltage peaks at 10.5409 V at n = 2.1082, and the 10 V setpoint is met twice, at n = 1.5195 and n = 2.9250, which multiply to RL/RR_L/R. For the 100% load the peak is the setpoint exactly, at n = 2.0000. For the 110% load the peak is 9.5346 V and the setpoint is met nowhere.

The load resistance in each curve is chosen so that at the ten-volt setpoint it takes a stated fraction of those 25 watts. For a load that takes 90 per cent, the voltage peaks at 10.54 volts at a ratio of 2.108, and the setpoint is met at two ratios: 1.519, on the rising side, and 2.925, on the falling side. The figure checks that the two multiply to RL/RR_L/R — they are the two roots of one quadratic — so they sit symmetrically about the peak on a logarithmic axis. For a load that takes exactly the nose power the peak is the setpoint, at a ratio of 2. For a load that takes 110 per cent the voltage never reaches ten volts at any ratio: the most it can be given is 9.535.

This curve is the whole argument drawn once. A regulator does not know the curve; it knows only whether the voltage is below the setpoint, and if it is, it raises the ratio. On the rising side that is the right thing to do. On the falling side it is exactly the wrong thing, and nothing in the regulator’s sensing distinguishes the two sides.

The regulator, marched

The regulator integrates its error: its ratio changes at kk per volt-second of difference between the setpoint and the load’s voltage, dn/dt=k(VsetV)dn/dt = k(V_{set} - V). The march is a fourth-order rule on the ratio, with the load’s voltage solved from the ratio at every step, and it starts from unity ratio, where the voltage is sagging.

A regulator holding 10 V on a load that asks for 101% of the nose power collapses it in 256 s; at 110%, in 79 sMarched with a fourth-order rule. A 10 V source behind 1 Ω feeds a load resistance through an ideal ratio n, and a regulator raises n at 0.05 per volt-second of error to hold the load at 10 V. The load's resistance is chosen so that at 10 V it takes the stated fraction of the most the line can deliver, 25 W. At 90% the regulator settles at n = 1.5195, below the nose ratio √(Rₗ/R) = 2.1082. At 99% the regulator settles at n = 1.8182, below the nose ratio √(Rₗ/R) = 2.0101. At 101% the voltage climbs to 9.950 V — the most the line allows that load, V₀√(Rₗ/R)/2 — at 101.7 s, and falls below half the setpoint at 256.3 s while the regulator keeps raising the ratio. At 110% the voltage climbs to 9.535 V — the most the line allows that load, V₀√(Rₗ/R)/2 — at 23.5 s, and falls below half the setpoint at 78.6 s while the regulator keeps raising the ratio. The regulator's gain, the slope of the load's voltage against the ratio, is positive below √(Rₗ/R) and negative above it.05100100200time (seconds)load voltage (volts)the setpoint90% of the nosesettles, n = 1.51999%settles, n = 1.818101%peak 9.95 V, half at 256 s110%peak 9.53 V, half at 79 smarched — a ratio integrated against its own errorthe gain changes sign at the nose
Fig. 3 The load’s voltage against time for a regulator of 0.05 per volt-second holding 10 V, with the load asking for 90%, 99%, 101% and 110% of the line’s most power. At 90% it settles at n = 1.5195 and at 99% at n = 1.8182, both below the nose ratio. At 101% the voltage climbs to 9.950 V at 101.7 s and falls below half the setpoint at 256.3 s; at 110% it peaks at 9.535 V at 23.5 s and is below half at 78.6 s. The slider is the regulator’s rate.

Asked for 90 per cent of the nose, the regulator does its job: the voltage rises and settles at the setpoint with the ratio at 1.5195, the smaller of the two roots, which the figure checks to a part in ten thousand. At 99 per cent it settles too, at 1.8182, still below the nose ratio of 2.0101 but much closer to it; the settling is slower, because near the peak the voltage responds to the ratio only weakly.

At 101 per cent the setpoint does not exist anywhere on the curve, and the march shows what that means in time. The voltage rises as the regulator raises the ratio, slows as it approaches the peak, and reaches 9.950 volts at 101.7 seconds — exactly the most the line allows this load, V0RL/R/2V_0\sqrt{R_L/R}/2, which the figure checks. The regulator, still seeing a voltage below its setpoint, keeps raising the ratio. The voltage turns over and falls, the error grows, the regulator raises the ratio faster, and the load’s voltage is below half its setpoint at 256.3 seconds. At 110 per cent the same sequence is shorter: a peak of 9.535 volts at 23.5 seconds and half the setpoint at 78.6.

Every check in the figure is about the regulator’s gain changing sign. At each load it checks numerically that the slope of the voltage against the ratio is positive a thousandth below RL/R\sqrt{R_L/R} and negative a thousandth above it. The collapse is not a failure of the regulator’s tuning or a limit of its rate; it is that the plant the regulator controls reverses its gain at the nose, and an integrator with a reversed gain is an integrator running away.

What the collapse looks like from the control room

It is worth reading the 101 per cent curve as an operator would see it, because nothing on it looks like the failure it is. For the first hundred seconds the voltage rises steadily from its sag towards ten volts, which is what a regulator is for. It slows as it approaches, which is what an integrating regulator nearing its setpoint does. At its best it reads 9.950 volts — half a per cent short of the setpoint, well inside the band most regulators are set to tolerate — and the ratio indicator shows a tap still moving in the direction that has been raising the voltage all along. Only after that does the voltage begin to fall, and for tens of seconds the fall is slower than the rise was.

Every quantity the regulator displays in the first two minutes is the display of a regulator working. The quantity that would have said otherwise is the slope of the voltage against the ratio, and it passes through zero at the moment the voltage is closest to the setpoint — so the best reading of the whole event and the loss of control happen together.

The setpoint is part of the demand

The load in every run is a resistance, and a resistance does not ask for a power; it asks for whatever power the voltage across it gives. The regulator is what turns it into a demand, and the size of the demand is the setpoint squared over the resistance. So the fraction of the nose a regulated load asks for is set as much by the regulator’s setpoint as by the load.

The 110 per cent load makes the point with its own numbers. At a ten-volt setpoint it asks for a tenth more than the line can deliver and collapses. The most voltage the line can give it is 9.535 volts, and at that voltage the same resistance takes exactly the nose power: a regulator set to 9.53 volts would hold it, at the peak, with no margin, and one set to nine volts would hold it comfortably at 89 per cent of the nose. The load did not change and the line did not change. Lowering the setpoint by a twentieth moved the demand from past the nose to on it, because the demand goes as the square of the setpoint.

That is the arithmetic behind the practice of reducing a network’s voltage setpoints when it is heavily loaded, and it runs against the instinct that a sagging voltage should be pushed back up. The instinct is right below the nose, where the push is rewarded with voltage. Near the nose the push is rewarded with less voltage, and a lower setpoint is the one action that moves the equilibrium back onto the side where the regulator’s gain has the right sign.

A setpoint met on the wrong side

Below the nose there is a second failure, and it does not need the load to ask for too much.

At 90% of the nose power the regulator holds from n = 1 and collapses the voltage from 1% above n = 2.925. Marched with a fourth-order rule: the regulator of rate 0.05 per volt-second, a load taking 90% of the line's most power at the 10 V setpoint, started from four ratios. The setpoint is met at n = 1.5195 and n = 2.9250. From unity ratio (n = 1.0000) it settles at n = 1.5195. From 1% below the second ratio (n = 2.8957) it settles at n = 1.5195. From 1% above it (n = 2.9542) the voltage falls below half the setpoint at 92.4 s. From half as much again (n = 4.3874) the voltage falls below half the setpoint at 23.9 s. Nothing about the load or the line differs between the runs; only where the regulator was when it began.
Fig. 4 The same regulator and a load taking 90% of the line’s most power, started from four ratios. The setpoint is met at n = 1.5195 and n = 2.9250. From unity ratio, and from 1% below the second ratio, it settles at n = 1.5195. From 1% above the second ratio the voltage falls below half the setpoint at 92.4 s; from half as much again, at 23.9 s.

The load asks for 90 per cent of the nose, and the setpoint is met at two ratios. The larger, 2.925, is an equilibrium — the voltage there is exactly the setpoint and the regulator does not move — but it is on the falling side of the peak, where a small increase in the ratio lowers the voltage and the regulator responds by increasing the ratio further. Started one per cent below it, where the voltage is slightly above the setpoint, the regulator lowers the ratio, crosses the peak, and settles at 1.519. Started one per cent above it, where the voltage is slightly below, the regulator raises the ratio and the voltage falls below half its setpoint at 92.4 seconds. Started half as far again, at 23.9 seconds.

So the second root is an edge, exactly as the bus’s lower operating point was, and for the same structural reason: it is the equilibrium on the side of the maximum where the incremental response has the wrong sign. The difference is what puts a system there. A bus has its operating point set by its load; a regulator has its ratio set by its own history. A tap changer that was left at a high tap during a period of low demand, or that was driven up during a fault that depressed the voltage, can find itself above the second root when the load returns — and then a load comfortably inside the line’s capacity collapses the voltage anyway.

How long the collapse takes

The time between the demand exceeding the nose and the voltage falling is the operator’s only window, and it has a law.

Past the nose a regulator takes 256 s to collapse the voltage at 1% over and 2521 s at 0.01% — the inverse square root of the excess. Marched, for the regulator of rate 0.05 per volt-second holding a 10 V load on a 10 V, 1 Ω line. The time from the regulator starting at unity ratio to the load's voltage falling below half the setpoint, against how far the load's demand is past the nose power. 0.010% past: 2520.7 s. 0.030% past: 1458.2 s. 0.10% past: 801.5 s. 0.30% past: 465.1 s. 1.0% past: 256.3 s. 3.0% past: 148.1 s. 10% past: 78.6 s. 30% past: 39.7 s. Close to the nose the time grows as the −0.497 power of the excess, which is the passage time through the bottleneck a vanished equilibrium leaves: π/(k·√(½|V''|·ΔV)) with ΔV the gap between the setpoint and the most the line allows, drawn dashed — 2513 s at 0.01% before the approach from unity ratio is added.
Fig. 5 The time from unity ratio to the load’s voltage falling below half the setpoint, against how far the demand is past the nose. 0.01% past: 2,521 s; 0.1%: 801.5 s; 1%: 256.3 s; 10%: 78.6 s; 30%: 39.7 s. Near the nose the time grows as the −0.497 power of the excess, beside the closed form for the passage through a vanished equilibrium’s bottleneck.

At a hundredth of a per cent past the nose the collapse takes 2,521 seconds; at a tenth of a per cent, 801.5; at one per cent, 256.3; at ten, 78.6. Close to the nose the time grows as the −0.497 power of the excess, and the figure checks the exponent at a half to within five hundredths.

The square root is not a fit, it is a mechanism. Just past the nose the regulator’s equation near the peak is dn/dtk(ΔV+12V(nn)2)dn/dt \approx k\bigl(\Delta V + \tfrac12|V''|(n - n^\ast)^2\bigr), where ΔV\Delta V is the small gap between the setpoint and the most the line allows. When the demand is at the nose that gap is zero and the regulator stops at the peak; just past it, the equilibrium has vanished but its ghost remains, and the ratio crawls through the region where the equilibrium used to be. The time to cross it is π/(k12VΔV)\pi/\bigl(k\sqrt{\tfrac12|V''|\,\Delta V}\bigr), and since ΔV\Delta V grows in proportion to the excess, the time grows as its inverse square root. The figure draws that closed form dashed and checks that at a hundredth of a per cent it agrees with the march to two per cent: 2,513 seconds against 2,521.

The practical reading is uncomfortable. A load that is just past the nose collapses slowly — for this regulator, forty minutes at a hundredth of a per cent — and the voltage during most of that time is close to its setpoint and rising towards its peak. Nothing in the voltage looks like an emergency until the regulator is well past the peak. The slowest collapses are the ones with the smallest margin to recover, and they give the most time to notice and the least evidence to notice it by.

A regulator holding 10 V on a load that asks for 101% of the nose power collapses it in 641 s; at 110%, in 196 s. Marched with a fourth-order rule. A 10 V source behind 1 Ω feeds a load resistance through an ideal ratio n, and a regulator raises n at 0.02 per volt-second of error to hold the load at 10 V. The load's resistance is chosen so that at 10 V it takes the stated fraction of the most the line can deliver, 25 W. At 90% the regulator settles at n = 1.5195, below the nose ratio √(Rₗ/R) = 2.1082. At 99% the regulator settles at n = 1.8182, below the nose ratio √(Rₗ/R) = 2.0101. At 101% the voltage climbs to 9.950 V — the most the line allows that load, V₀√(Rₗ/R)/2 — at 254.4 s, and falls below half the setpoint at 640.7 s while the regulator keeps raising the ratio. At 110% the voltage climbs to 9.535 V — the most the line allows that load, V₀√(Rₗ/R)/2 — at 58.6 s, and falls below half the setpoint at 196.5 s while the regulator keeps raising the ratio. The regulator's gain, the slope of the load's voltage against the ratio, is positive below √(Rₗ/R) and negative above it.
Fig. 6 The same four demands with a regulator of 0.02 per volt-second. At 101% the voltage peaks at 254.4 s and is below half the setpoint at 640.7 s; at 110% it peaks at 58.6 s and is below half at 196.5 s.

A slower regulator stretches every time in proportion — 640.7 seconds instead of 256.3 at one per cent past the nose, with the rate cut from 0.05 to 0.02 — because the rate sets the time scale and nothing else in the equation has one. That is the argument for a slow regulator on a heavily loaded line, and the limit of it: slowing the regulator buys time to act and does not change whether the collapse happens.

What the measurement contains, and what it leaves out

A resistive load behind an ideal ratio on a resistive line. That is the smallest system in which a regulator’s gain changes sign, and every number here is exact for it. A reactive line has the nose of the load that has two voltages or none at a different place and the peak of the voltage against the ratio with it, and a line with its own charge has the moved nose of the headroom that is the line’s own charge; the sign change happens at the nose in both, and the ratio at which it happens moves.

A continuous ratio. A tap changer moves in steps, with a deadband and a delay, and its march is a staircase rather than a curve. The steps do not remove the mechanism — each step past the peak lowers the voltage and provokes the next — and they make the bottleneck coarser, so the square-root law should hold only when many steps fit inside the bottleneck.

A load that restores its power instantly. Real loads restore over their own time constants — a thermostat’s cycle, a motor’s slip — and the constant-power behaviour exists only on timescales longer than those. When the regulator is faster than the load’s restoration, the regulator sees a resistance and there is no nose to push past; the collapse needs the regulator to be slower than the load. That ordering of time constants is the practical condition for this failure, and it is not modelled.

No limit on the ratio. Every real regulator has a highest tap. The march here raises the ratio without bound; a real one reaches its limit and stops, with the voltage wherever the curve is at that ratio — which past the nose is lower than it would have been had the regulator never acted.

Still open: the blocking rule, the reactive line, and the load that restores slowly

A regulator that blocks. The standard protection against this failure is to block the regulator when the voltage fails to respond to a tap change in the expected direction. That rule is a measurement of the sign of the gain on the running system. Marching a regulator with such a rule — step, observe, block if the voltage fell — would say how much of the collapse time the rule needs before it can act, and whether a noisy voltage makes it block below the nose, where the gain is small but positive.

A reactive line with a leading load. The far end of a reactive line feeding a leading load can read above its source at the nose, and a regulator watching that voltage sees no sag to correct until it is far past the nose. Whether a regulator on such a line ever acts before collapse, or only afterwards, is the dynamic version of the far end that rises, and it combines the worst of both measurements.

A load with its own time constant. A load that restores its power over a time comparable with the regulator’s gives the system two slow states instead of one, and the bottleneck above becomes a question about which of the two reaches the ghost of the equilibrium first. The same march with a first-order restoring load would find the ratio of time constants below which the regulator cannot collapse the voltage at all.

Part 4 on voltage regulation

One argument about Voltage regulation, and one of 4 essays on it so far, each part numbered by how much of the idea it assumes. What sits either side of it:

The objects named here

The third axis, after the field and the idea: the things themselves, and every essay that touches each one.

Design tradeoffLine impedanceMaximum power transferModel rangeOperating pointVoltage regulation