The capacitor that was right once
Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.
The reactor that keeps a bank out of it
A correction bank on a stiff bus resonates with the supply at a harmonic set by the two sizes, and at 640 kvar on 16 MVA that harmonic is the fifth, which it multiplies by 34. A reactor of 7 per cent of the capacitor's reactance in series puts a null at h = 3.78, and above that null the bank is an inductor, in parallel with another inductor, with nothing left to resonate. So the fifth is never raised at any size of bank. It was not free. The capacitor now stands 7.5 per cent above the bus, the resonance has gone below the null and can land on the third, 22.7 times at 654 kvar, and the number that looks like a detail, 7 rather than the 4 that would tune the bank to the fifth, is what keeps an ageing bank on the right side of its null.