Series resonance — where it appears
Named by 4 essays across 2 fields — each of them below, with the objects they name alongside it.
The capacitor that was right once
Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.
The reactance cancelled, and the resonance it buys
Putting a capacitor in series with a feeder cancels part of its reactance and the far end falls less: five per cent of regulation becomes four and a quarter at a quarter compensation and 2.7 per cent at seventy per cent. What comes with it is a series resonance that was not there before, at the line frequency times the root of the fraction cancelled — so a quarter compensation resonates at exactly half the line frequency and a ninth at exactly a third. The line's own inductance is not in that answer and neither is the voltage.
The input that pushes back
An emitter follower with a capacitor on its emitter has a negative resistance looking into its base — 1182 ohms of it at 3.4 megahertz for a nanofarad, with nothing added to the model. A negative resistance is not an oscillator until a reactance cancels, and the base lead supplies it: with ten ohms of source the loop goes unstable above 74.9 nanohenries, which is seven centimetres of wire. The repair is the opposite of the instinct — a hundred ohms of source raises the threshold to 913 nanohenries, so the fix for a follower that oscillates is to make the thing driving it worse.
The energy a unity power factor doubles
Reactive power was computed three ways on this site and the agreement was called a verification. Two of the three are one theorem written twice and cannot disagree about anything; only the third is independent, and what it computes is a difference. Correcting a 20 Ω, 50 mH load to a power factor of 1.000000 takes its reactive power from 1,285 var to nothing and takes the energy stored in the installation from 2,044.9 mJ to 4,089.7 mJ — exactly twice, at every load and every frequency.