Concept

Power factor — where it appears

The real power a load takes divided by the product of its voltage and current, which is one only for a current in phase with the voltage and sinusoidal. It is cos φ only while the current is a sinusoid, and a rectifier's is not: its displacement factor can be exactly one while its true factor is 0.78.

Named by 12 essays across 3 fields — each of them below, with the objects they name alongside it.

A 20 Ω, 50 mH load on 230 V at 50 Hz. computed by solving, not by drawing. The load draws 1636 W and 1285 var, an apparent power of 2080 VA at a power factor of 0.786. The reactive side is confirmed by a route that touches no impedance: 2ω times the energy stored in the inductor gives 1285 var. The cable carries 9.04 A and only 7.11 A of it does anything.

The current that does no work

A solved network has been reporting its own real power on every page of this collection, as the second of the two checks each answer passes before it is drawn. What that check discards is the imaginary half — the power that flows out to a reactance and back again, does nothing, and is still carried by the cable, still heats the transformer, and is still on the bill.

power · Reactive power
One capacitor of 77.3 µF, against every load it was not sized for. computed by solving, not by drawing. Sized from the 20 Ω load, the capacitor takes the power factor to 1.000000 there and leaves 0.0e+0 var of 1636 VA. At 178 Ω the same installation sits at 0.23 leading. The correction is exact at one point on this axis and nowhere else on it.

The capacitor that was right once

Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.

power · Power factor correction
Three balanced rectifier loads conducting 60°, and their neutral. computed by solving, not by drawing. The three phase currents are drawn faint and the neutral heavy. Balanced loads, identical in every respect, and the neutral carries 0.968 A against a line current of 0.559 A — a ratio of 1.7321, where √3 is 1.7321. The pulse trains are disjoint, so the neutral is their union and its mean square is three times one phase's. Rebuilding the same current from the multiples of three in one phase's spectrum gives 0.966 A, 0.13% away, by a route sharing only the waveform.

The neutral that carries more than a line

Three balanced loads draw currents summing to 5.3 × 10⁻¹⁵ amperes in the neutral. That is a theorem about sinusoids, and it uses nothing except that each current is a single frequency. A harmonic of order three is shifted by 360° between phases, which is no shift at all — so the third harmonics add, and for any conduction angle narrow enough that the pulse trains stay disjoint the neutral carries exactly √3 times a line current.

power · Three-phase
1000 µF across a 100 Ω load, rectified from 17 V peak. The output sits at 15.69 V with 1.331 V of ripple, against the 1.569 V the expression I/2fC gives — 15.1% high, because the capacitor is being recharged for part of the cycle rather than discharging throughout it. The lower panel is why: the diode conducts for 28.8° of each half cycle and carries 2.10 A at the peak, which is 13.4 times the 157 mA the load draws.

The direct voltage that is a sawtooth

A rectifier and a reservoir capacitor make what everybody calls a direct voltage. Marched with the diodes in the netlist, a thousand microfarads across a hundred ohms gives 15.69 volts with 1.33 volts of ripple on it, against the 1.57 the textbook expression predicts. The expression is high by the fraction of the cycle the diode conducts for — measured at 0.94 to 0.96 of it across two sweeps — and it has no opinion at all about the quantity that actually sizes the transformer, which is a peak diode current 13.4 times the current the load draws.

applied · Unregulated supply
50 Ω + j100 Ω of line, and the load angle past which the far end rises. computed by solving, not by drawing at 71 load resistances and four load angles. A source of 50 Ω + j100 Ω feeding loads of the same resistance and different power factor: at unity power factor the voltage across the load climbs towards the source's and stops there, reaching 0.9675 of it at the largest load drawn. A lagging load leaves less. A leading one leaves more, and past a computable angle it leaves more than the source has: the condition is 2Rₗ(Rₛ + Xₛ·tanφ) + |Zₛ|² < 0, which for the largest load here is 28.35° of lead — bisected on the solve at 28.35° — tending to atan(Rₛ/Xₛ) = 26.57° as the load grows. So the edge is a property of the line and the load angle together, and "voltage regulation" quoted as a percentage carries neither.

The far end that rises

Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.

power · Voltage regulation
Flat in angle at √(L/C), 141.42 Ω, and flat in size at 91.018 Ω. computed by solving, not by drawing, at 127 resistances on the closed form the network was checked against. The upper curve is the frequency at which the part's size is 1% away from R, the lower one the frequency at which its angle reaches 1°. Both are V-shaped and their points are in different places: the angle's first-order term vanishes at √(L/C) = 141.42 Ω, bisected on the measured slope to ten figures, and the size's second-order term at 91.018 Ω. The widest 1° band is 1.13 GHz, at 150.69 Ω; the widest 1% band is 1.66 GHz, at 95.806 Ω. At 91.018 Ω, flattest in size, the angle reaches 1° by 53.9 MHz. The flat line is 139 MHz, where a 6 mm body is one degree long: it binds the angle's edge from 118.72 Ω to 168.88 Ω and the size's from 43.947 Ω to 359.53 Ω.

The resistor that is right in size and wrong in angle

A resistor's impedance departs from its value in size as the square of frequency and in angle as the first power, so the angle always leaves first: at ten milliohms and at a megohm alike, where the angle has reached a degree the size is still only 152 parts per million out. One time constant, L/R − RC, sets that degree — 4.00 nanoseconds and 695 kilohertz at ten kilohms, 800 nanoseconds and 3.47 kilohertz for a ten-milliohm shunt. The resistance flattest in angle is exactly √(L/C), 141.42 ohms, the value the size question rejected; at the 91.02 ohms flattest in size the angle reaches a degree by 53.9 megahertz, and no resistance is flat in both.

frequency · Real resistor
50 Ω + j100 Ω of line: every power below the nose at two voltages, and a leading load's nose at 1.055 of the source. computed by solving, not by drawing: a load of fixed angle swept in size from open circuit to short circuit on a line of 50 Ω + j100 Ω, with the power it takes against the voltage it is left with, for four load angles. Each curve rises to a most power and turns back while the voltage keeps falling, so every smaller power is delivered at two voltages and every larger one at none. A 30° lagging load reaches 0.4222 of a matched resistive line's power with 0.5221 of the source voltage left; a unity power factor load reaches 0.6180 of a matched resistive line's power with 0.5878 of the source voltage left; a 30° leading load reaches 0.8240 of a matched resistive line's power with 0.7293 of the source voltage left; a 60° leading load reaches 0.9960 of a matched resistive line's power with 1.0553 of the source voltage left. Each nose is found by golden-section search on the solved network, agrees with V²cos φ/(2|Z|(1 + cos(θ − φ))), and falls where the load impedance's magnitude equals the line's.

The load that has two voltages or none

A load that takes a fixed power takes more current as its voltage falls, and on a line with impedance in it every power below a limit is delivered at two voltages and every power above it at none. The limit sits at the load the maximum-power theorem describes, half the source voltage on a resistive line. On fifty ohms and a hundred of reactance a load leading by sixty degrees reaches that limit with its far end at 1.055 of the source, and at nine tenths of it reads 1.172 — so a far end that reads high is not a far end with margin. On a direct-current bus the lower of the two voltages is not a state at all: one per cent below it the bus runs down to nothing in 3.48 milliseconds.

power · Voltage regulation
With its own capacitance at B|Z| = 0.2, a line's nose for a unity-power-factor load moves from 0.618 to 0.658 of a matched line's power, at 0.635 of the source. computed by solving, not by drawing: a unity-power-factor load swept in size from open circuit to short circuit on a line of 50 Ω + j100 Ω carrying its own shunt capacitance as a π, half at each end, with the total susceptance stated as B|Z|. At B|Z| = 0 the nose is 0.6180 of a matched resistive line's power with 0.5878 of the source voltage left, and the unloaded far end reads 1.0000. At B|Z| = 0.1 the nose is 0.6376 of a matched resistive line's power with 0.6108 of the source voltage left, and the unloaded far end reads 1.0465. At B|Z| = 0.2 the nose is 0.6582 of a matched resistive line's power with 0.6353 of the source voltage left, and the unloaded far end reads 1.0969. At B|Z| = 0.4 the nose is 0.7025 of a matched resistive line's power with 0.6895 of the source voltage left, and the unloaded far end reads 1.2107. Each nose is found by golden-section search on the solved network and agrees with the nose of the Thevenin equivalent V/(1 + jBZ/2) behind Z/(1 + jBZ/2).

The headroom that is the line's own charge

A line of 50 + j100 ohms delivers at most 0.6180 of a matched resistive line's power to a unity-power-factor load, with 0.5878 of the source voltage left. Give the line its own shunt capacitance — a π, half at each end, B|Z| = 0.4 in all — and the nose moves to 0.7025 at 0.6895: 13.7 per cent more power and 17.3 per cent more voltage. It is headroom, but not the headroom the far end advertises, which with no load rises 21.1 per cent. The capacitance turns the source and line into a Thevenin equivalent with more voltage behind more impedance, and it moves a voltage threshold's meaning in opposite directions depending on whether it is referred to the source or to the unloaded far end.

power · Voltage regulation
Cancelling 50% of the line's reactance: a 0.3 lagging load's regulation goes from 7.78% to 4.18%, a unity one's from 2.17% to 1.96%, a 0.7 leading one's from −3.78% to −1.26%. computed by solving, not by drawing, at 50 Hz: a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, its regulation against the load's power factor from 0.7 leading to 0.3 lagging, with no compensation (dashed) and with 50% of the line's reactance cancelled by a series capacitor (solid). The solve agrees with the voltage divider in closed form to 9e-10 of a per cent. At 0.3 lagging the regulation falls from 7.781% to 4.176%; at 0.9 lagging, from 5.168% to 3.381%; at unity, only from 2.171% to 1.960%; and at 0.7 leading the far end, above the source at −3.778%, comes down to −1.255%. The capacitor cancels what the load's reactive current does in the line's reactance, in either direction, and pulls every load towards the regulation the line's resistance alone would give.

The drop a series capacitor can reach

A series capacitor cancels part of a line's reactance, so it can only cancel the part of the drop that the reactance makes — and that part is set by the load, not the line. On a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, half compensation takes a 0.3 lagging load from 7.78% regulation to 4.18% and a unity load only from 2.17% to 1.96%, and it brings a 0.71 leading load's raised far end back down. Cancel all of it and a leading load and its lagging twin sit at exactly the same voltage. Cancel more and the far end rises with its load; at exactly 100% the resonance is the fundamental and a far-end fault draws 4,600 A. Where the capacitor goes, the load cannot tell.

power · Series compensation
A capacitor of 67% of the load's reactive power, moved along a feeder whose load is spread evenly over 10 km. computed by solving, not by drawing at each of 30 positions: one phase of an 11 kV feeder of 0.3 + j0.35 Ω/km, carrying 2 MW at 0.8 lagging spread over 30 equal loads. Uncorrected it loses 16.8 kW a phase; with every load corrected to unity at its own terminals, 11.1 kW — so 5.66 kW is the reactive current's share. This capacitor does best at 67% of the way out, where the loss is 11.8 kW and 87.6% of the reactive share is gone. At the substation end it removes nothing; at the far end it overshoots.

The capacitor two-thirds of the way out

A feeder's reactive current costs loss in every section it passes through, and on a feeder whose load is spread along its length that current is largest at the substation and falls to nothing at the far end. Correcting it at the substation removes no loss at all. One phase of an 11 kV feeder carrying 2 MW at 0.8 lagging over ten kilometres loses 16.8 kW, of which 5.66 kW is the reactive current's; the best single capacitor is about two-thirds of the load's reactive power placed about two-thirds of the way out, and it removes 87.6% of that share — against the eight-ninths the textbook rule gives for an idealised line. Two capacitors at 2/5 and 4/5 remove 95.6%. The same capacitor left in at light load costs more than it saves below half load, and the rule for a continuous load is a statement about many taps.

power · Reactive power
The harmonics of one phase of three balanced rectifier loads conducting 60°, each sorted into the sequence its three phasors form. computed by solving, not by drawing: each harmonic of the three phases decomposed into zero, positive and negative sequence. Every one is a single sequence to the arithmetic's floor: h1 positive, h3 zero, h5 negative, h7 positive, h9 zero, h11 negative, h13 positive, h15 zero. A balanced set shifts harmonic h by h × 120° between phases, so the third and its multiples are not shifted at all — zero sequence — the seventh is shifted as the fundamental is, and the fifth the other way round. Relative to the fundamental, the zero-sequence harmonics together are 72.5%, the negative 24.1% and the positive 16.7%.

The sequence a harmonic belongs to

Symmetrical components are defined on phasors, so they describe one frequency, and a rectifier load's current has many. Taken harmonic by harmonic, three balanced loads give a single sequence at every harmonic, to the arithmetic's floor: the third and its multiples zero sequence, the seventh, thirteenth and nineteenth positive, the fifth, eleventh and seventeenth negative — because harmonic h is shifted h × 120° between phases. The sequence decides where each harmonic can go. Connected line to line, the loads put no triplen in a line at all: 3.32 A of them circulates round the delta and never leaves it. Fed through a delta–wye transformer beside a second group, the fifth and seventh cancel in the supply and the eleventh and thirteenth remain, because the transformer turns the two sequences opposite ways.

power · Three-phase
A 640 kvar bank on a 16 MVA 400 V bus: alone its resonance with the supply is at h = 5.00, and with a 7% reactor in series at 3.01, with the bank's own null at 3.78 between that and everything above it. computed by solving, not by drawing: the impedance per phase at a 400 V bus, with a short-circuit level of 16 MVA and a 640 kvar correction bank, against harmonic order, in closed form and at the fifth by a netlist. The bank alone (dashed) resonates with the supply at h = 5.00, where the bus impedance peaks. With a reactor of 7% of the capacitor's fundamental reactance in series (solid), the bank's own series resonance is at h = 1/√0.07 = 3.78, a deep null, and the parallel peak has moved down to h = 3.01. Above the null the bank is an inductor, in parallel with the supply's inductance, so there is nothing for any higher harmonic to resonate with.

The reactor that keeps a bank out of it

A correction bank on a stiff bus resonates with the supply at a harmonic set by the two sizes, and at 640 kvar on 16 MVA that harmonic is the fifth, which it multiplies by 34. A reactor of 7 per cent of the capacitor's reactance in series puts a null at h = 3.78, and above that null the bank is an inductor, in parallel with another inductor, with nothing left to resonate. So the fifth is never raised at any size of bank. It was not free. The capacitor now stands 7.5 per cent above the bus, the resonance has gone below the null and can land on the third, 22.7 times at 654 kvar, and the number that looks like a detail, 7 rather than the 4 that would tune the bank to the fifth, is what keeps an ageing bank on the right side of its null.

power · Power factor correction

Named alongside it

The objects these essays reach for when they reach for this one.

Reactive powerVoltage regulationModel rangeLine impedanceMaximum power transferPhasorPower factor correctionSeries resonanceApparent powerDesign tradeoffHarmonic amplificationNeutral current

All concepts