Power, and the part that does no work
The current that does no work
A solved network has been reporting its own real power on every page of this collection, as the second of the two checks each answer passes before it is drawn. What that check discards is the imaginary half — the power that flows out to a reactance and back again, does nothing, and is still carried by the cable, still heats the transformer, and is still on the bill.
The capacitor that was right once
Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.
Three phases, and the wire that carries nothing
Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.
The neutral that carries more than a line
Three balanced loads draw currents summing to 5.3 × 10⁻¹⁵ amperes in the neutral. That is a theorem about sinusoids, and it uses nothing except that each current is a single frequency. A harmonic of order three is shifted by 360° between phases, which is no shift at all — so the third harmonics add, and for any conduction angle narrow enough that the pulse trains stay disjoint the neutral carries exactly √3 times a line current.
The load that takes the most
A load equal to the source resistance takes more power than any other, and it does so at exactly fifty per cent efficiency — the source burns as much as the load receives. Ninety per cent efficiency needs a load nine times the source and delivers 36% of what was available, and a load half the source resistance delivers exactly as much as one twice it.
What a meter multiplies by
An average-responding meter rectifies, averages and multiplies by 1.1107, which makes it exactly right for a sinusoid and wrong for everything else by the ratio of two form factors — 11.07 per cent high on a square wave and 35.9 per cent low on a rectifier drawing its current in sixty degrees. It is also exactly right at one other waveform, a 145.90 degree conduction angle, which is nobody's sinusoid. Beside it a true-RMS meter that reaches nine harmonics is two per cent low on a square wave and never within one per cent of anything narrower.
The far end that rises
Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.
The reactance cancelled, and the resonance it buys
Putting a capacitor in series with a feeder cancels part of its reactance and the far end falls less: five per cent of regulation becomes four and a quarter at a quarter compensation and 2.7 per cent at seventy per cent. What comes with it is a series resonance that was not there before, at the line frequency times the root of the fraction cancelled — so a quarter compensation resonates at exactly half the line frequency and a ninth at exactly a third. The line's own inductance is not in that answer and neither is the voltage.
The first cycle, which no steady state contains
Every number this field computes about a rectifier — the ripple, the crest factor, the conduction angle, the power factor — is read from the settled state, and the march that produces them starts from an empty capacitor and throws the first cycle away. That first conduction carries 32.4 amperes against a repetitive peak of 1.23, it is 26 times larger than anything the circuit ever does again, and how large it is depends on when somebody's hand closed the switch.
The inductance that limits, and lifts
Adding winding resistance to a rectifier limits the first peak and does not reduce the energy at all — the essay below measured ∫i²dt as two per cent apart over a factor of four in the resistance. Adding leakage inductance does both: it divides the peak by seven and the energy by five, and dissipates nothing to do it. What it buys instead is a rectifier whose output sits 29 per cent above the peak of its own supply, permanently, which every steady-state expression in this field says cannot happen.
The pair that is worse than either
A bulk capacitor and a ceramic are fitted together because each is good where the other is not, and between them is a frequency at which the pair presents six times the impedance either one does alone. The peak is a parallel resonance between one part's inductance and the other's capacitance, its height is one over the series resistance every data sheet asks to be minimised, and at it the two capacitors exchange 5.87 amps for every amp the load draws.
The capacitor that is not where the load is
A decoupling bank is usually drawn as two capacitors joined to a load through nothing, which is a stated simplification. Put three nanohenries of ordinary copper in — one of mounting loop per part and two of plane between the bank and the load — and the anti-resonance moves down to 5.63 megahertz and up to 1.29 ohms, a probe touching the ceramic reads a twelfth of what the load sees at 16.7 megahertz and three and a half times too much at 8.35, and the twentieth capacitor is worse than the second.
The protection that is gone by the second time
An inrush thermistor is ten ohms cold and holds the first cycle down; then the load current warms it and it settles at 83 degrees and 1.94 ohms, which is 19 per cent of what was bought. That is the design working. It is also a part that takes 198 seconds to recover half its cold resistance, against a reservoir capacitor that empties in tens of milliseconds — so a mains dip in that window hands the rectifier an unlimited inrush into an empty capacitor, which is the exact event the part is on the bill of materials for.
The degrees a thermocouple cannot see
Every thermal answer in this collection has been one temperature, and a core makes its heat in its volume and loses it from a surface, so it has two. Solved as a conduction problem, a twenty-millimetre core in still air is 2.59 kelvin hotter in the middle than on the outside — 2.9 per cent of a ninety-kelvin rise, which is why the lumped answer has been good enough. Cool the same core on a plate and the gradient does not shrink; it grows to 3.37 kelvin and becomes 78 per cent of what is left.
The floor and the ceiling move apart
A decoupling bank is judged by two numbers — the lowest impedance it reaches and the highest frequency at which it still meets its target — and with no copper between the parts and the load both improve together as capacitors are added, 5.000 milliohms down to 1.500 and 19.8 megahertz up to 162. Three nanohenries of ordinary board separate them. The bank's own floor still falls 3.33 times while the load's falls 1.49, and the ceiling read at the parts climbs to 82.4 megahertz while the load's peaks at 8.06 and falls to 5.05. At twenty parts the two nodes disagree by a factor of 94 about the same solve.
The loop gain one temperature understates
Every thermal loop gain this collection has computed was computed at a single temperature, because a lumped fixed point has only one — and the essay that measured the gradient inside a core recorded, without measuring it, that this makes each of those numbers a lower bound. It is a lower bound by three per cent where a ferrite usually sits and by thirty-eight per cent at the well-cooled end, always in the direction that makes the part safer than the calculation said. The obvious candidate for what decides it is refused: three geometries at one Biot number are 3.3 times apart.
The energy a unity power factor doubles
Reactive power can be computed three ways, and their agreement is easily called a verification. Two of the three are one theorem written twice and cannot disagree about anything; only the third is independent, and what it computes is a difference. Correcting a 20 Ω, 50 mH load to a power factor of 1.000000 takes its reactive power from 1,285 var to nothing and takes the energy stored in the installation from 2,044.9 mJ to 4,089.7 mJ — exactly twice, at every load and every frequency.
The half the neutral does not carry
A star load unbalanced in one phase produces two things, not one. The neutral carries three times the zero-sequence current, which is the half a neutral ammeter reads; the other half is a negative-sequence set of exactly the same size, rotating backwards, that the neutral never sees. With 0.5 Ω of line in front of 20 Ω loads, losing a phase entirely puts 50.00 per cent negative sequence in the current and 0.8265 per cent in the voltage a switchboard meter reads.
The average a square root pulls low
A true-RMS converter squares, averages and takes the root, and the root of a quantity that ripples averages below the root of its mean. With a hundred-millisecond averager a sine is read one per cent low below 1.86 hertz, where the ripple is still ±20 per cent — and a second filter that steadies the display takes the ripple away and leaves the reading exactly as low as it was. A square wave is read exactly at any averaging time; a rectifier current conducting for twenty degrees needs 2.41 times the averaging a sine does. The implicit converter is the explicit one at half the time constant, and a reading falls 1.38 times slower than it rises.
The load that has two voltages or none
A load that takes a fixed power takes more current as its voltage falls, and on a line with impedance in it every power below a limit is delivered at two voltages and every power above it at none. The limit sits at the load the maximum-power theorem describes, half the source voltage on a resistive line. On fifty ohms and a hundred of reactance a load leading by sixty degrees reaches that limit with its far end at 1.055 of the source, and at nine tenths of it reads 1.172 — so a far end that reads high is not a far end with margin. On a direct-current bus the lower of the two voltages is not a state at all: one per cent below it the bus runs down to nothing in 3.48 milliseconds.
The load that may be complex
Freed of the constraint that it be a resistance, the best load is the source's conjugate — found here by a two-dimensional search on the solved network rather than assumed — and it takes the available power at exactly fifty per cent efficiency whatever the source's reactance. A load that may only be a resistance takes 2/(1 + √(1+x²)) of that, and at a source reactance of twice its resistance that is exactly the golden ratio less one, 0.618034. The resistor-only load is also the MORE efficient of the two, rising towards one while the conjugate sits at a half for ever.
The headroom that is the line's own charge
A line of 50 + j100 ohms delivers at most 0.6180 of a matched resistive line's power to a unity-power-factor load, with 0.5878 of the source voltage left. Give the line its own shunt capacitance — a π, half at each end, B|Z| = 0.4 in all — and the nose moves to 0.7025 at 0.6895: 13.7 per cent more power and 17.3 per cent more voltage. It is headroom, but not the headroom the far end advertises, which with no load rises 21.1 per cent. The capacitance turns the source and line into a Thevenin equivalent with more voltage behind more impedance, and it moves a voltage threshold's meaning in opposite directions depending on whether it is referred to the source or to the unloaded far end.
The regulator that pushes past the nose
A regulator that raises a ratio whenever its load's voltage is low is a stabiliser only while raising the ratio raises the voltage, and on a line that stops being true at exactly the nose: the load's voltage, n·V₀ times the load resistance over n²R plus that resistance, peaks at a turns ratio of the square root of the load over the line and falls beyond it. Ask the load for 90 per cent of the nose power and the regulator settles at n = 1.519 — unless it starts above n = 2.925, where the same setpoint is met on the wrong side of the peak, and then it collapses the voltage. Ask for 101 per cent and the voltage climbs to 9.950 volts, the most the line allows, and is below half its setpoint 256 seconds later. Near the nose the collapse takes a time that grows as the inverse square root of the excess: 2,521 seconds at a hundredth of a per cent.
The noise a true-RMS meter reads low
A true-RMS converter reads a sine low by an amount that falls as the square of its frequency, and for anything but a slow sine that amount vanishes: 3.96 parts per million at ten times the averager's corner. Noise is not a sine. Its square fluctuates at every frequency down to zero, and the averager passes a share of that set by its own bandwidth against the noise's, so the reading is low by 1/(16Bτ) — the first power, not the second. Measured on seeded noise at Bτ = 10 it is 0.600 per cent low against a predicted 0.625; at 100, 672 parts per million. One reading scatters by eighteen times that, so no single reading shows the bias and the mean of a few hundred is nothing but bias.
The cycle a converter has to know
Summing a waveform's square over a whole number of periods reads its root-mean-square exactly: no averager, no ripple, no bias. It needs the period, and a period known one per cent long puts a hundredth of a period too much into the window. Wherever that extra piece falls, the reading moves — on a sine by up to 0.50 per cent over one period, and by 0.46 per cent over ten, because the extra piece grows with the window as fast as the window does. The worst error is δ(CF² − 1)/2, set by the crest factor and the period error and not by how many periods are summed, until the excess reaches half a period. A square wave is read exactly from any window, and a 60° rectifier current twice as badly as a sine.
The reactance that is not free
A conjugate match cancels the source's reactance with an opposite one and takes all the available power, where a resistor alone takes 2/(1 + √(1 + x²)), 0.618 of it when the reactance is twice the resistance. The cancelling capacitor is not free. With quality factor Q it carries a resistance of its reactance over Q, and cancelling fully then delivers 1/(1 + x/Q). That beats the resistor alone only above Q = 2(√(1 + x²) + 1)/x, 3.236 here, twice the golden ratio. But full cancellation is not the best use of a lossy capacitor. Cancelling part of the reactance beats both, and helps at all above Q = (√(1 + x²) + 1)/x, the golden ratio itself. Below that, the right amount to cancel is none.
The load for a source that will not hold still
A conjugate match is exact at one frequency. Held fixed while the frequency moves, it stays within a decibel of the available power over 1.0176/x of the centre: 51 per cent of it when the source's reactance is twice its resistance, 12.7 per cent at eight times. It beats the resistor-only load only between 0.73 and 1.84 of the centre frequency. The resistor-only load is not a broadband answer, as it is usually called. It is a low-pass whose best frequency is direct current. And for a source whose reactance could be anywhere within ±Δx of a centre, the fixed load that guarantees the most power cancels the centre exactly and takes a resistance of √(1 + Δx²) times the source's. That guarantees 2/(1 + √(1 + Δx²)): the resistor-only rule, applied to the uncertainty instead of to the reactance.
The window that forgives the period
A converter that sums a waveform's square over whole periods reads its RMS exactly, and one that sums over periods 1.3% too long reads a sine 0.6% wrong — δ/2, for any number of periods — because the extra sliver of period counts at full weight. Weight the window down to zero at its ends and the sliver barely counts. Over eight periods a triangular weight reads the same sine 79 ppm wrong and a Hann weight 23 ppm; and they are different kinds of cure. The triangle is the only one that changes the error's order, from first to second in δ, so it wins when the period is nearly right; the Hann weight keeps first order but falls with the number of periods, about as its inverse square, so it wins over long windows. Both cost nothing with the period exact — from two periods up. Over one, a Blackman–Harris weight reads even a sine 10% wrong. The price is noise: a Hann-weighted reading of noise scatters √1.5 as widely.
The drop a series capacitor can reach
A series capacitor cancels part of a line's reactance, so it can only cancel the part of the drop that the reactance makes — and that part is set by the load, not the line. On a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, half compensation takes a 0.3 lagging load from 7.78% regulation to 4.18% and a unity load only from 2.17% to 1.96%, and it brings a 0.71 leading load's raised far end back down. Cancel all of it and a leading load and its lagging twin sit at exactly the same voltage. Cancel more and the far end rises with its load; at exactly 100% the resonance is the fundamental and a far-end fault draws 4,600 A. Where the capacitor goes, the load cannot tell.
Sixty degrees, and the limit compensation stops raising
Series capacitors are put in transmission lines to raise how much power can pass between two sources before the angle between them runs out. The lossless textbook limit, V²/X(1 − k), rises without bound as the reactance is cancelled. With the line's resistance kept, the limit is V² cos β (1 − cos β)/R for an impedance angle β, and it peaks where β is exactly sixty degrees: 56.7 per cent cancellation and 264.5 kW on a 230 V tie of 0.05 + j0.2 Ω, against 194.4 uncompensated — then falls, to nothing at full cancellation. A line of R/X 0.1 can nearly triple its limit; one above 1/√3 cannot raise it at all. And at the best compensation the line delivers exactly half of what it is sent.
What each element buys against the limit
A source whose resistance sits behind twice as much inductive reactance can deliver, over ±25 per cent of its centre frequency, 54.2 per cent of its available power to the best plain resistor and at worst 82.8 per cent through the best single capacitor. That single-element answer is exactly the fixed load for an uncertain reactance: the capacitor makes the reactance swing ±1 across the band and the load is √2 times the source. Two elements lift the worst case to 89.5, three to 97.3, and a fourth, in a chain of single elements, to 97.4. Bode and Fano bound every lossless network at 99.81 per cent over that band — a limit three elements come within a tenth of a decibel of and no finite network reaches.
The reactance the capacitor cannot reach
A series capacitor raises a tie's transfer limit until the loop's impedance angle is sixty degrees, and on a bare 0.05 + j0.2 Ω line that is 56.7% cancellation. Put a machine at each end, its EMF held behind a reactance of its own, and the capacitor still cancels only the line: the sixty degrees now needs the line's reactance plus twice a machine's, less √3 times the resistance, as a fraction of the line's reactance, which passes 100% as soon as each machine's reactance exceeds √3/2 of the line's resistance — 0.043 Ω here. Beyond that the limit rises at every step to full cancellation, and the lossless estimate of the gain, wildly high on a bare line, becomes nearly right: 1.43 against 1.50 at 0.2 Ω. The higher limit is reached with the receiving terminal lower — 180 V falling to 148 at 0.1 Ω — and the capacitor's own resistance is negligible for any power capacitor: a Q of 222 keeps the peak within 1%.
The peak a sagging receiver keeps
The sixty degrees at which series compensation stops raising a tie's transfer limit is a statement about two ends at equal voltage. With the receiving end lower, the limit is a parabola in the cosine of the impedance angle whose top is at cos β = Vₛ/2Vᵣ: 56.3° and 62.6% cancellation for a receiver at 0.9 of the sender, 33.6° and 83.4% at 0.6, full cancellation at one half. But the height of that top is Vₛ²/4R whatever the receiving voltage — 264.5 kW for the 0.05 + j0.2 Ω tie from a receiver at 1.1 of the sender down to one at 0.5 — and at it the receiving end takes exactly half of what is sent, to four decimal places, for every receiving voltage tried. The best compensated tie is the sending source driving a matched load, and the receiving source's voltage only decides how much capacitor that takes.
The capacitor two-thirds of the way out
A feeder's reactive current costs loss in every section it passes through, and on a feeder whose load is spread along its length that current is largest at the substation and falls to nothing at the far end. Correcting it at the substation removes no loss at all. One phase of an 11 kV feeder carrying 2 MW at 0.8 lagging over ten kilometres loses 16.8 kW, of which 5.66 kW is the reactive current's; the best single capacitor is about two-thirds of the load's reactive power placed about two-thirds of the way out, and it removes 87.6% of that share — against the eight-ninths the textbook rule gives for an idealised line. Two capacitors at 2/5 and 4/5 remove 95.6%. The same capacitor left in at light load costs more than it saves below half load, and the rule for a continuous load is a statement about many taps.
The instant a transformer is worst at
A capacitor-input rectifier draws its worst inrush when it is switched on at the peak of the mains. A transformer's own magnetising branch is the other way round: switched on at the voltage zero, a 230 V primary worked at 1.4 T draws 87.6 A in its first half-cycle, 791 times its settled magnetising current, and at the voltage peak it draws nothing extra at all. The core's flux has to start from zero, the voltage does not, and how close the working flux sits to half of saturation decides the size.
The harmonic that names an inrush
A transformer's differential relay sees an inrush as current going in and nothing coming out, which is what an internal fault looks like, and it tells them apart by the second harmonic. Marched cycle by cycle, an inrush starts at 79% second harmonic and stays above the usual 15% restraint for thirty cycles — long after its current has fallen from 88 A to 205 mA, because the current unwinds in a few cycles and the flux offset under it takes seconds. A fault's offset is a smooth exponential and peaks at 14.6% only when X/R is as low as three.
The sequence a harmonic belongs to
Symmetrical components are defined on phasors, so they describe one frequency, and a rectifier load's current has many. Taken harmonic by harmonic, three balanced loads give a single sequence at every harmonic, to the arithmetic's floor: the third and its multiples zero sequence, the seventh, thirteenth and nineteenth positive, the fifth, eleventh and seventeenth negative — because harmonic h is shifted h × 120° between phases. The sequence decides where each harmonic can go. Connected line to line, the loads put no triplen in a line at all: 3.32 A of them circulates round the delta and never leaves it. Fed through a delta–wye transformer beside a second group, the fifth and seventh cancel in the supply and the eleventh and thirteenth remain, because the transformer turns the two sequences opposite ways.
The peak a load step does not see
A decoupling bank is specified by its impedance against frequency, and the number that fails a target is the anti-resonance peak — 0.966 Ω at 7.12 MHz for the bulk-and-ceramic pair standing on a regulator. A load that steps by one ampere moves that supply by 132 mV, 14% of what the peak suggests: a step rings the resonance once, and its first swing is set by the resonance's characteristic impedance √(L/C) = 0.224 Ω, not by its Q. The peak is the voltage per ampere of a load that sits at the resonance; switched at 7.12 MHz the same load builds over six cycles to ±611 mV, the peak times the current's fundamental. So damping, the cure for the peak, is a cure for that load only: sixteen times the ESR cuts the peak 8.9-fold and leaves a step's swing between 120 and 155 mV. What decides a step is its edge — 132 mV for anything faster than a few nanoseconds, 28 mV for a microsecond.
The rule that reads the sign of the gain
A regulator that raises a ratio whenever its load is low collapses the voltage once the load asks for more than the line's nose power, because past the nose raising the ratio lowers the voltage. The standard protection is a rule: after each tap, compare the voltage with the one before, and if it fell, stop. On a 10 V line asked for 105% of its 25 W, a 1.25% tap changer with the rule stops at n = 1.9625, the first tap past the nose, and holds 9.759 V — the most the line can give — where without it the ratio climbs to 3.25 and the voltage is 8.61 V and still falling. The rule is exact without noise and fragile with it, because it reads a difference that vanishes at the nose: with 3 mV of measurement noise it wrongly stops a raise that could have reached the setpoint 0.3% of the time at 98% of the nose and 15% at 99.5%. Trusting it to 1% costs margin — 97.9% of the nose at 3 mV, 79.9% at 10 mV — or coarser taps.
The reactor that keeps a bank out of it
A correction bank on a stiff bus resonates with the supply at a harmonic set by the two sizes, and at 640 kvar on 16 MVA that harmonic is the fifth, which it multiplies by 34. A reactor of 7 per cent of the capacitor's reactance in series puts a null at h = 3.78, and above that null the bank is an inductor, in parallel with another inductor, with nothing left to resonate. So the fifth is never raised at any size of bank. It was not free. The capacitor now stands 7.5 per cent above the bus, the resonance has gone below the null and can land on the third, 22.7 times at 654 kvar, and the number that looks like a detail, 7 rather than the 4 that would tune the bank to the fifth, is what keeps an ageing bank on the right side of its null.