Field

Power, and the part that does no work

A nodal solve computes real power as a check on its own answer and then throws it away. This field reads it out — and then the imaginary half beside it, which sizes the cable, heats the transformer and is billed for. A correction capacitor is exact at the load it was computed for and at no other; a power factor is cos φ only while the current is a sinusoid, and a rectifier's is not.
A 20 Ω, 50 mH load on 230 V at 50 Hz. computed by solving, not by drawing. The load draws 1636 W and 1285 var, an apparent power of 2080 VA at a power factor of 0.786. The reactive side is confirmed by a route that touches no impedance: 2ω times the energy stored in the inductor gives 1285 var. The cable carries 9.04 A and only 7.11 A of it does anything.

The current that does no work

A solved network has been reporting its own real power on every page of this collection, as the second of the two checks each answer passes before it is drawn. What that check discards is the imaginary half — the power that flows out to a reactance and back again, does nothing, and is still carried by the cable, still heats the transformer, and is still on the bill.

One capacitor of 77.3 µF, against every load it was not sized for. computed by solving, not by drawing. Sized from the 20 Ω load, the capacitor takes the power factor to 1.000000 there and leaves 0.0e+0 var of 1636 VA. At 178 Ω the same installation sits at 0.23 leading. The correction is exact at one point on this axis and nowhere else on it.

The capacitor that was right once

Cancelling a load's reactive power needs one division and no iteration, and the answer is exact. It is exact for the load it was computed from, at the frequency it was computed at, and the figure here is about what it does everywhere else — which includes making the installation worse than it was before anything was fitted.

The neutral of a three-phase supply with one phase 30% off. computed by solving, not by drawing. Balanced, the three line currents sum to 4.6e-16 of one of them and the neutral carries nothing. With one phase 30% heavier the neutral carries 2.65 A against a line current of 11.50 A. The neutral reaches a tenth of a line current at 11.1% imbalance.

Three phases, and the wire that carries nothing

Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.

Three balanced rectifier loads conducting 60°, and their neutral. computed by solving, not by drawing. The three phase currents are drawn faint and the neutral heavy. Balanced loads, identical in every respect, and the neutral carries 0.968 A against a line current of 0.559 A — a ratio of 1.7321, where √3 is 1.7321. The pulse trains are disjoint, so the neutral is their union and its mean square is three times one phase's. Rebuilding the same current from the multiples of three in one phase's spectrum gives 0.966 A, 0.13% away, by a route sharing only the waveform.

The neutral that carries more than a line

Three balanced loads draw currents summing to 5.3 × 10⁻¹⁵ amperes in the neutral. That is a theorem about sinusoids, and it uses nothing except that each current is a single frequency. A harmonic of order three is shifted by 360° between phases, which is no shift at all — so the third harmonics add, and for any conduction angle narrow enough that the pulse trains stay disjoint the neutral carries exactly √3 times a line current.

The load that takes the most power, and the load that wastes the least. computed by solving, not by drawing at 71 load values. The power into the load peaks at a ratio of 1.000000, which is the magnitude of the source impedance to six figures, and the efficiency there is 0.500000 — the source dissipates as much as the load receives. Ninety per cent efficiency needs a ratio of 9.7 and delivers 34% of the available power.

The load that takes the most

A load equal to the source resistance takes more power than any other, and it does so at exactly fifty per cent efficiency — the source burns as much as the load receives. Ninety per cent efficiency needs a load nine times the source and delivers 36% of what was available, and a load half the source resistance delivers exactly as much as one twice it.

Two meters, one current, and neither of them measuring the heat. computed by solving, not by drawing, at 35 conduction angles. The first curve is an average-responding meter: it rectifies, averages and multiplies by 1.1107, which is exactly right for a sinusoid — -7.8e-5% here — and exactly 11.07% high on a square wave, because the error is the ratio of two form factors and contains neither the amplitude nor the frequency. On a rectifier drawing its 100 W in sixty degrees of conduction it is -35.90% low. The second curve is a true-RMS meter that reaches 9 harmonics, which has no shape assumption in it and a bandwidth instead: it returns the root-sum-square of the lines it can see, and is one per cent low below every angle here of conduction. The crest factor at sixty degrees is 1.733, which is inside every instrument's rating — neither meter is failing because the peak is large. One is failing because the shape is not a sinusoid and the other because the spectrum is wider than it is.

What a meter multiplies by

An average-responding meter rectifies, averages and multiplies by 1.1107, which makes it exactly right for a sinusoid and wrong for everything else by the ratio of two form factors — 11.07 per cent high on a square wave and 35.9 per cent low on a rectifier drawing its current in sixty degrees. It is also exactly right at one other waveform, a 145.90 degree conduction angle, which is nobody's sinusoid. Beside it a true-RMS meter that reaches nine harmonics is two per cent low on a square wave and never within one per cent of anything narrower.

50 Ω + j100 Ω of line, and the load angle past which the far end rises. computed by solving, not by drawing at 71 load resistances and four load angles. A source of 50 Ω + j100 Ω feeding loads of the same resistance and different power factor: at unity power factor the voltage across the load climbs towards the source's and stops there, reaching 0.9675 of it at the largest load drawn. A lagging load leaves less. A leading one leaves more, and past a computable angle it leaves more than the source has: the condition is 2Rₗ(Rₛ + Xₛ·tanφ) + |Zₛ|² < 0, which for the largest load here is 28.35° of lead — bisected on the solve at 28.35° — tending to atan(Rₛ/Xₛ) = 26.57° as the load grows. So the edge is a property of the line and the load angle together, and "voltage regulation" quoted as a percentage carries neither.

The far end that rises

Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.

25% compensation: 4.26% regulation, and a resonance at 25.0 Hz. computed by solving, not by drawing. The current a 230 V feeder draws, swept from two hertz to a hundred and fifty, with 25% of the line's reactance cancelled by a series capacitor. The regulation falls from 5.17% to 4.26%, which is what the capacitor was fitted for. What comes with it is a series resonance at 9.59 Hz with the load connected and 24.99 Hz with the far end shorted — the latter being exactly f₀√k = 25.00 Hz, a frequency the compensation fraction chooses on its own. The line's inductance does not appear in it and neither does the voltage. It is always below the fundamental, which is where the machines are.

The reactance cancelled, and the resonance it buys

Putting a capacitor in series with a feeder cancels part of its reactance and the far end falls less: five per cent of regulation becomes four and a quarter at a quarter compensation and 2.7 per cent at seventy per cent. What comes with it is a series resonance that was not there before, at the line frequency times the root of the fraction cancelled — so a quarter compensation resonates at exactly half the line frequency and a ninth at exactly a third. The line's own inductance is not in that answer and neither is the voltage.

The first conduction carries 26× the repetitive peak, and the factor of 7 is the user's. computed by solving, not by drawing. The largest diode current in the first conduction after switch-on, against the phase of the mains at the instant of switching, marched from an empty capacitor through the same netlist the ripple and the conduction angle are read from. The settled circuit's largest current is 1.230 A; the first one is 32.39 A at the worst instant and 4.64 A at the best, so which of them a design has to survive is decided by nothing in the design. The estimate that treats the capacitor as a short circuit gives 34.00 A, 4.7% high, the difference being the charge the capacitor takes during the pulse itself. Holding the first peak to ten times the repetitive one would need 1.90 Ω of winding resistance.

The first cycle, which no steady state contains

Every number this field computes about a rectifier — the ripple, the crest factor, the conduction angle, the power factor — is read from the settled state, and the march that produces them starts from an empty capacitor and throws the first cycle away. That first conduction carries 32.4 amperes against a repetitive peak of 1.23, it is 26 times larger than anything the circuit ever does again, and how large it is depends on when somebody's hand closed the switch.

The inductance divides the current by 7 and leaves the capacitor 29% above the mains peak. computed by solving, not by drawing. The first conduction of a rectifier whose transformer has a leakage inductance as well as a winding resistance, marched from an empty capacitor at the worst instant of the mains. The peak falls from 36.4 A at 20 µH to 5.3 A at 5000, and — unlike the winding resistance measured on the first cycle alone, which limits the current and leaves ∫i²dt exactly where it was — the inductance takes the energy down with it, from 0.370 to 0.073 A²s. What it costs is the second curve: the inductor's current cannot stop at the instant the two voltages are equal, so the capacitor overshoots to 21.86 V at 1000 µH — 28.6% above the 17 V peak of its own supply — and the diodes will not let the charge back out. The overshoot has an interior maximum, because past it the mains reverses before the ring has finished.

The inductance that limits, and lifts

Adding winding resistance to a rectifier limits the first peak and does not reduce the energy at all — the essay below measured ∫i²dt as two per cent apart over a factor of four in the resistance. Adding leakage inductance does both: it divides the peak by seven and the energy by five, and dissipates nothing to do it. What it buys instead is a rectifier whose output sits 29 per cent above the peak of its own supply, permanently, which every steady-state expression in this field says cannot happen.

A bulk capacitor and a ceramic, and the peak between them at 6.52 MHz. computed by solving, not by drawing. Each capacitor is three elements — its capacitance, its series resistance and its series inductance — and a one-amp source drives the node, so the node voltage is the impedance. Alone, each dips to its own series resistance at its own self-resonance and rises on either side. Together they do not: between the two resonances the bulk part is an inductor and the ceramic is still a capacitor, and an inductance across a capacitance is a parallel resonance. The pair reaches 1.187 Ω at 6.52 MHz, where the bulk alone would give 0.2023 Ω and the ceramic alone 0.2055 — 5.87 times worse than either. The dashed curves are the two parts on their own; the solid one is what the load actually sees.

The pair that is worse than either

A bulk capacitor and a ceramic are fitted together because each is good where the other is not, and between them is a frequency at which the pair presents six times the impedance either one does alone. The peak is a parallel resonance between one part's inductance and the other's capacitance, its height is one over the series resistance every data sheet asks to be minimised, and at it the two capacitors exchange 5.87 amps for every amp the load draws.

Three nanohenries of copper move the peak to 5.63 MHz and raise it to 1.29 Ω. computed by solving, not by drawing. The same two capacitors, with and without the inductance of the way to them: one nanohenry of mounting loop per part and two nanohenries of plane between the bank and the load. The dashed curve is the bank with no inductance in the way, peaking at 1.187 Ω at 6.52 MHz; the solid one is what the load sees, peaking at 1.293 Ω at 5.63 MHz. The peak moves down because the branch that is inductive at that frequency got more inductive, and it rises for the same reason. Above about twenty megahertz the two part company entirely: the bank is still falling toward its parts' own resistances and the load is rising on two nanohenries that no capacitor is across.

The capacitor that is not where the load is

A decoupling bank is usually drawn as two capacitors joined to a load through nothing, which is a stated simplification. Put three nanohenries of ordinary copper in — one of mounting loop per part and two of plane between the bank and the load — and the anti-resonance moves down to 5.63 megahertz and up to 1.29 ohms, a probe touching the ceramic reads a twelfth of what the load sees at 16.7 megahertz and three and a half times too much at 8.35, and the twentieth capacitor is worse than the second.

An inrush limiter's steady state, and how little of it is still a limiter. computed by solving, not by drawing. A negative-temperature-coefficient thermistor in series with a supply, at 1 ampere of load current. The falling curve is what it dissipates at a temperature — I²R with R following the two-point β fit a catalogue prints — and the rising line is what its mounting removes. They cross once, at 83.1 degrees, and the loop gain there is -1.374: negative, so the part is stable at every current rather than below a boundary. What is left of its cold 10 ohms at that temperature is 1.937 — 19.4 per cent. The slider moves the load current, and more current leaves less resistance.

The protection that is gone by the second time

An inrush thermistor is ten ohms cold and holds the first cycle down; then the load current warms it and it settles at 83 degrees and 1.94 ohms, which is 19 per cent of what was bought. That is the design working. It is also a part that takes 198 seconds to recover half its cold resistance, against a reservoir capacitor that empties in tens of milliseconds — so a mains dip in that window hands the rectifier an unlimited inrush into an empty capacitor, which is the exact event the part is on the bill of materials for.

The temperature through a 20 mm core that makes its own heat. computed by solving, not by drawing. Conduction with volumetric generation, solved on forty-one cells with a surface film at each face and the loss density evaluated at each cell's own temperature — so the middle of the core makes less heat than its faces do, which a closed form for uniform generation cannot express. The peak is 115.05 °C and the surface 112.45: a gradient of 2.59 kelvin, which is 2.9 per cent of the 90.0 kelvin rise. That share is Bi/(Bi + 2) — 3.0 per cent at a Biot number of 0.063 — so it is decided by how well the surface is cooled and not by how much heat is made.

The degrees a thermocouple cannot see

Every thermal answer in this collection has been one temperature, and a core makes its heat in its volume and loses it from a surface, so it has two. Solved as a conduction problem, a twenty-millimetre core in still air is 2.59 kelvin hotter in the middle than on the outside — 2.9 per cent of a ninety-kelvin rise, which is why the lumped answer has been good enough. Cool the same core on a plate and the gradient does not shrink; it grows to 3.37 kelvin and becomes 78 per cent of what is left.

The bank reaches 1.500 mΩ and the load sees 141.5 mΩ at that same frequency. computed by solving, not by drawing. One bulk part and 20 ceramics, with a nanohenry of mounting loop each and two nanohenries of plane between the bank and the load, solved once per frequency and read at both nodes. The dashed curve is the bank's own node — what a probe on the parts measures. The solid one is the load. The bank's least impedance is 1.500 mΩ at 11.3 MHz, and at that frequency the load sees 141.5 mΩ, which is 94.3 times more, against 141.5 mΩ of plane reactance at that frequency. Whatever the parts do, the load's reading cannot fall below the reactance of the copper in front of them, and the parts reach their best by moving up the frequency axis into it.

The floor and the ceiling move apart

A decoupling bank is judged by two numbers — the lowest impedance it reaches and the highest frequency at which it still meets its target — and with no copper between the parts and the load both improve together as capacitors are added, 5.000 milliohms down to 1.500 and 19.8 megahertz up to 162. Three nanohenries of ordinary board separate them. The bank's own floor still falls 3.33 times while the load's falls 1.49, and the ceiling read at the parts climbs to 82.4 megahertz while the load's peaks at 8.06 and falls to 5.05. At twenty parts the two nodes disagree by a factor of 94 about the same solve.

What one temperature costs the loop gain of a part that has a gradient. computed by solving, not by drawing. The thermal loop gain of a 30 mm core, solved as a body with its own internal temperature profile and again as a single lump at that profile's mean, against the Biot number. Both are negative, so the core is a stabilising feedback either way — but the body's loop is the more negative of the two at every point, by 3.0 per cent at a Biot number of 0.108 and 38 per cent at 10.8. A lumped calculation therefore understates how stable a wound part is, and the amount it understates by is not a property of the material but of how well the surface is cooled relative to how well the inside conducts. Below a Biot number of about a tenth it is worth under two per cent and the lump is the right model; at the cooled end the part has 7 kelvin inside it and half the feedback is invisible to a single temperature.

The loop gain one temperature understates

Every thermal loop gain this collection has computed was computed at a single temperature, because a lumped fixed point has only one — and the essay that measured the gradient inside a core recorded, without measuring it, that this makes each of those numbers a lower bound. It is a lower bound by three per cent where a ferrite usually sits and by thirty-eight per cent at the well-cooled end, always in the direction that makes the part safer than the calculation said. The obvious candidate for what decides it is refused: three geometries at one Biot number are 3.3 times apart.

Correcting a 20 Ω, 50 mH load to unity, and what it stores. computed by solving, not by drawing. A capacitor across a 230 V, 50 Hz supply is swept from nothing to 300 µF against a load drawing 1636 W and 1285 var. The reactive power falls through zero at 77.31 µF and keeps going; the energy stored in the installation rises from 2044.9 mJ to 4089.7 mJ at that point — exactly twice, because unity power factor means the two stores are equal — and goes on rising afterwards. Only the cable current has a least value, 7.113 A against 9.044 A.

The energy a unity power factor doubles

Reactive power can be computed three ways, and their agreement is easily called a verification. Two of the three are one theorem written twice and cannot disagree about anything; only the third is independent, and what it computes is a difference. Correcting a 20 Ω, 50 mH load to a power factor of 1.000000 takes its reactive power from 1,285 var to nothing and takes the energy stored in the installation from 2,044.9 mJ to 4,089.7 mJ — exactly twice, at every load and every frequency.

The two sequences a neutral current says nothing about. computed by solving, not by drawing at 61 imbalances. Three 20 Ω loads on a 230 V, 50 Hz star supply, one of them raised by a fraction of itself, with the neutral in place. The zero-sequence current is the one the neutral carries three times and is the only one a neutral ammeter reads; the negative sequence is a balanced set of three phasors rotating the other way. At 30.0 per cent imbalance it is 0.8846 A against 10.6154 A of positive sequence, 8.333 per cent, against 8.333 per cent from x/(3 + 2x). Two per cent arrives at 6.250 per cent imbalance, bisected on the network.

The half the neutral does not carry

A star load unbalanced in one phase produces two things, not one. The neutral carries three times the zero-sequence current, which is the half a neutral ammeter reads; the other half is a negative-sequence set of exactly the same size, rotating backwards, that the neutral never sees. With 0.5 Ω of line in front of 20 Ω loads, losing a phase entirely puts 50.00 per cent negative sequence in the current and 0.8265 per cent in the voltage a switchboard meter reads.

A true-RMS reading of a sine: ripple a second filter removes, and a bias it cannot. An explicit converter — square, average through a one-pole of τ = 100 ms, take the root — in steady state on a sine of unit root-mean-square value, integrated exactly over a period at 91 frequencies and by a fourth-order march of its own equation at 6, which agree to 1.9e-8. The upper curve is half the ripple on the reading and the lower one the amount by which its mean is low. The reading is low at every frequency, because the square root is concave; it is 1% low below 1.86 Hz, while the ripple is inside ±1% only above 39.8 Hz. The dashed curve is the small-ripple form, an eighth of the averaged square's ripple power, which the bias approaches as the ripple shrinks.

The average a square root pulls low

A true-RMS converter squares, averages and takes the root, and the root of a quantity that ripples averages below the root of its mean. With a hundred-millisecond averager a sine is read one per cent low below 1.86 hertz, where the ripple is still ±20 per cent — and a second filter that steadies the display takes the ripple away and leaves the reading exactly as low as it was. A square wave is read exactly at any averaging time; a rectifier current conducting for twenty degrees needs 2.41 times the averaging a sine does. The implicit converter is the explicit one at half the time constant, and a reading falls 1.38 times slower than it rises.

50 Ω + j100 Ω of line: every power below the nose at two voltages, and a leading load's nose at 1.055 of the source. computed by solving, not by drawing: a load of fixed angle swept in size from open circuit to short circuit on a line of 50 Ω + j100 Ω, with the power it takes against the voltage it is left with, for four load angles. Each curve rises to a most power and turns back while the voltage keeps falling, so every smaller power is delivered at two voltages and every larger one at none. A 30° lagging load reaches 0.4222 of a matched resistive line's power with 0.5221 of the source voltage left; a unity power factor load reaches 0.6180 of a matched resistive line's power with 0.5878 of the source voltage left; a 30° leading load reaches 0.8240 of a matched resistive line's power with 0.7293 of the source voltage left; a 60° leading load reaches 0.9960 of a matched resistive line's power with 1.0553 of the source voltage left. Each nose is found by golden-section search on the solved network, agrees with V²cos φ/(2|Z|(1 + cos(θ − φ))), and falls where the load impedance's magnitude equals the line's.

The load that has two voltages or none

A load that takes a fixed power takes more current as its voltage falls, and on a line with impedance in it every power below a limit is delivered at two voltages and every power above it at none. The limit sits at the load the maximum-power theorem describes, half the source voltage on a resistive line. On fifty ohms and a hundred of reactance a load leading by sixty degrees reaches that limit with its far end at 1.055 of the source, and at nine tenths of it reads 1.172 — so a far end that reads high is not a far end with margin. On a direct-current bus the lower of the two voltages is not a state at all: one per cent below it the bus runs down to nothing in 3.48 milliseconds.

The load that may be complex, and what a resistor alone gives up. computed by solving, not by drawing, with the best load searched over BOTH of its parts on the solved network rather than substituted. Against a source of 50 Ω + j100 Ω the search returns 50.00 − j100.0 Ω — the conjugate — which delivers the available 500.00 mW at exactly 50.00% efficiency, and does so at every source reactance. A load that may only be a resistance takes 2/(1 + √(1 + x²)) of that, matching the solved answer to 4.4e-16 at ten reactances — and at x = 2 that fraction is exactly the golden ratio less one, 0.618034. The resistor-only load is the MORE efficient of the two at every non-zero reactance, rising towards one while the conjugate match sits at a half for ever, so the familiar "maximum power at fifty per cent" belongs to the conjugate and not to the load.

The load that may be complex

Freed of the constraint that it be a resistance, the best load is the source's conjugate — found here by a two-dimensional search on the solved network rather than assumed — and it takes the available power at exactly fifty per cent efficiency whatever the source's reactance. A load that may only be a resistance takes 2/(1 + √(1+x²)) of that, and at a source reactance of twice its resistance that is exactly the golden ratio less one, 0.618034. The resistor-only load is also the MORE efficient of the two, rising towards one while the conjugate sits at a half for ever.

With its own capacitance at B|Z| = 0.2, a line's nose for a unity-power-factor load moves from 0.618 to 0.658 of a matched line's power, at 0.635 of the source. computed by solving, not by drawing: a unity-power-factor load swept in size from open circuit to short circuit on a line of 50 Ω + j100 Ω carrying its own shunt capacitance as a π, half at each end, with the total susceptance stated as B|Z|. At B|Z| = 0 the nose is 0.6180 of a matched resistive line's power with 0.5878 of the source voltage left, and the unloaded far end reads 1.0000. At B|Z| = 0.1 the nose is 0.6376 of a matched resistive line's power with 0.6108 of the source voltage left, and the unloaded far end reads 1.0465. At B|Z| = 0.2 the nose is 0.6582 of a matched resistive line's power with 0.6353 of the source voltage left, and the unloaded far end reads 1.0969. At B|Z| = 0.4 the nose is 0.7025 of a matched resistive line's power with 0.6895 of the source voltage left, and the unloaded far end reads 1.2107. Each nose is found by golden-section search on the solved network and agrees with the nose of the Thevenin equivalent V/(1 + jBZ/2) behind Z/(1 + jBZ/2).

The headroom that is the line's own charge

A line of 50 + j100 ohms delivers at most 0.6180 of a matched resistive line's power to a unity-power-factor load, with 0.5878 of the source voltage left. Give the line its own shunt capacitance — a π, half at each end, B|Z| = 0.4 in all — and the nose moves to 0.7025 at 0.6895: 13.7 per cent more power and 17.3 per cent more voltage. It is headroom, but not the headroom the far end advertises, which with no load rises 21.1 per cent. The capacitance turns the source and line into a Thevenin equivalent with more voltage behind more impedance, and it moves a voltage threshold's meaning in opposite directions depending on whether it is referred to the source or to the unloaded far end.

A regulator holding 10 V on a load that asks for 101% of the nose power collapses it in 256 s; at 110%, in 79 s. Marched with a fourth-order rule. A 10 V source behind 1 Ω feeds a load resistance through an ideal ratio n, and a regulator raises n at 0.05 per volt-second of error to hold the load at 10 V. The load's resistance is chosen so that at 10 V it takes the stated fraction of the most the line can deliver, 25 W. At 90% the regulator settles at n = 1.5195, below the nose ratio √(Rₗ/R) = 2.1082. At 99% the regulator settles at n = 1.8182, below the nose ratio √(Rₗ/R) = 2.0101. At 101% the voltage climbs to 9.950 V — the most the line allows that load, V₀√(Rₗ/R)/2 — at 101.7 s, and falls below half the setpoint at 256.3 s while the regulator keeps raising the ratio. At 110% the voltage climbs to 9.535 V — the most the line allows that load, V₀√(Rₗ/R)/2 — at 23.5 s, and falls below half the setpoint at 78.6 s while the regulator keeps raising the ratio. The regulator's gain, the slope of the load's voltage against the ratio, is positive below √(Rₗ/R) and negative above it.

The regulator that pushes past the nose

A regulator that raises a ratio whenever its load's voltage is low is a stabiliser only while raising the ratio raises the voltage, and on a line that stops being true at exactly the nose: the load's voltage, n·V₀ times the load resistance over n²R plus that resistance, peaks at a turns ratio of the square root of the load over the line and falls beyond it. Ask the load for 90 per cent of the nose power and the regulator settles at n = 1.519 — unless it starts above n = 2.925, where the same setpoint is met on the wrong side of the peak, and then it collapses the voltage. Ask for 101 per cent and the voltage climbs to 9.950 volts, the most the line allows, and is below half its setpoint 256 seconds later. Near the nose the collapse takes a time that grows as the inverse square root of the excess: 2,521 seconds at a hundredth of a per cent.

A true-RMS converter reads noise low by 1/(16Bτ): 0.600% at Bτ = 10 and 672 ppm at 100, where a sine at fτ = 100 is 0.0396 ppm. Seeded, and measured. An explicit true-RMS converter — square, one-pole average of time constant τ, root — reading Gaussian noise of unit power, against the product of the noise's bandwidth and τ, from 1 to 100. Each point is 2²¹ samples at eight times the bandwidth, with the reading compared against the record's own root-mean-square and its standard error from batch means. Bτ = 1: 4.550% ± 150 ppm (band from zero), 4.081% (band of the same width about 3B). Bτ = 2: 2.598% ± 114 ppm (band from zero), 2.411% (band of the same width about 3B). Bτ = 5: 1.149% ± 75.4 ppm (band from zero), 1.098% (band of the same width about 3B). Bτ = 10: 0.600% ± 53.1 ppm (band from zero), 0.576% (band of the same width about 3B). Bτ = 20: 0.309% ± 39.1 ppm (band from zero), 0.295% (band of the same width about 3B). Bτ = 50: 0.127% ± 26.3 ppm (band from zero), 0.119% (band of the same width about 3B). Bτ = 100: 672 ppm ± 19 ppm (band from zero), 623 ppm (band of the same width about 3B). The dashed line is 1/(16Bτ), an eighth of the averaged square's variance, which the readings approach above Bτ = 10 and fall short of below it. A sine read by the same converter at the same product of frequency and τ is low by 3.96 ppm at 10 and 0.0396 ppm at 100 — the square of the noise's rate rather than its first power.

The noise a true-RMS meter reads low

A true-RMS converter reads a sine low by an amount that falls as the square of its frequency, and for anything but a slow sine that amount vanishes: 3.96 parts per million at ten times the averager's corner. Noise is not a sine. Its square fluctuates at every frequency down to zero, and the averager passes a share of that set by its own bandwidth against the noise's, so the reading is low by 1/(16Bτ) — the first power, not the second. Measured on seeded noise at Bτ = 10 it is 0.600 per cent low against a predicted 0.625; at 100, 672 parts per million. One reading scatters by eighteen times that, so no single reading shows the bias and the mean of a few hundred is nothing but bias.

Summed over whole periods 1.3% too long, a sine is read to ±0.65% for up to 38 periods, whatever their number. Integrated exactly over each window, the worst over every starting phase. The error in a root-mean-square summed over N assumed periods 1.3% too long, against N, for a sine and a 60° rectifier current, beside an explicit converter averaging over a comparable time, τ of N/2 periods. For the sine the worst error is 0.643% at one period and stays near δ/2 until N approaches 1/(2δ) = 38; it vanishes where Nδ is a whole number of half-periods of the square, and beyond it is bounded by 1/(4πN). The rectifier current's is 1.274% at one period, near δ(CF² − 1)/2 with a crest factor of 1.732. The converter at τ = N/2 periods is low by 15.8 ppm on the sine at N = 10, with a ripple of ±0.796%; on the rectifier current, low by 46.3 ppm with ±1.665%.

The cycle a converter has to know

Summing a waveform's square over a whole number of periods reads its root-mean-square exactly: no averager, no ripple, no bias. It needs the period, and a period known one per cent long puts a hundredth of a period too much into the window. Wherever that extra piece falls, the reading moves — on a sine by up to 0.50 per cent over one period, and by 0.46 per cent over ten, because the extra piece grows with the window as fast as the window does. The worst error is δ(CF² − 1)/2, set by the crest factor and the period error and not by how many periods are summed, until the excess reaches half a period. A square wave is read exactly from any window, and a 60° rectifier current twice as badly as a sine.

A lossy cancelling capacitor beats a resistor alone only above Q = 3.236 if it cancels everything, and only above 1.618 at all. computed by solving, not by drawing. A source of 50 Ω + j100 Ω, its reactance cancelled by a capacitor whose quality factor is Q, so that the capacitor carries a series resistance of its reactance over Q. Cancelling fully, with the load resistor matched to the source and capacitor resistances together, the load takes 1/(1 + x/Q) of the available power, at exactly half efficiency; a resistor alone takes 0.6180, 2/(1 + √(1 + x²)). They are equal at Q = 3.2361, twice the golden ratio. Cancelling only part of the reactance does better than either: it helps at all above Q = (√(1 + x²) + 1)/x = 1.6180, and at Q = 3 takes 0.6650 against 0.5971 cancelled fully.

The reactance that is not free

A conjugate match cancels the source's reactance with an opposite one and takes all the available power, where a resistor alone takes 2/(1 + √(1 + x²)), 0.618 of it when the reactance is twice the resistance. The cancelling capacitor is not free. With quality factor Q it carries a resistance of its reactance over Q, and cancelling fully then delivers 1/(1 + x/Q). That beats the resistor alone only above Q = 2(√(1 + x²) + 1)/x, 3.236 here, twice the golden ratio. But full cancellation is not the best use of a lossy capacitor. Cancelling part of the reactance beats both, and helps at all above Q = (√(1 + x²) + 1)/x, the golden ratio itself. Below that, the right amount to cancel is none.

Matched at 1 kHz, the conjugate load wins only from 730 Hz to 1.84 kHz; the resistor-only load is a low-pass, not a broadband answer. computed by solving, not by drawing. A source of 50 Ω and an inductance of 100 Ω at 1 kHz, with the conjugate load for 1 kHz — 50 Ω and a capacitor of −j100 Ω — and the resistor-only load for 1 kHz, 111.8 Ω, both held fixed while the frequency moves. The conjugate match takes all the available power at 1 kHz and stays within a decibel of it from 777 Hz to 1.29 kHz, a band of 50.9% of the centre, 1.0176/x. The resistor-only load takes 0.6180 at 1 kHz, 0.8509 at 100 Hz, and less at every frequency above: a low-pass whose peak is at direct current. The conjugate load is the better of the two only between 730 Hz and 1.84 kHz.

The load for a source that will not hold still

A conjugate match is exact at one frequency. Held fixed while the frequency moves, it stays within a decibel of the available power over 1.0176/x of the centre: 51 per cent of it when the source's reactance is twice its resistance, 12.7 per cent at eight times. It beats the resistor-only load only between 0.73 and 1.84 of the centre frequency. The resistor-only load is not a broadband answer, as it is usually called. It is a low-pass whose best frequency is direct current. And for a source whose reactance could be anywhere within ±Δx of a centre, the fixed load that guarantees the most power cancels the centre exactly and takes a resistance of √(1 + Δx²) times the source's. That guarantees 2/(1 + √(1 + Δx²)): the resistor-only rule, applied to the uncertainty instead of to the reactance.

With the period 1.3% long, eight periods read a sine 0.599% wrong through a rectangle, 79.4 ppm through a triangle, 22.8 ppm through a Hann window. Integrated over each weighted window, the worst over every starting phase. The error in a sine's root-mean-square summed over N assumed periods 1.3% too long, against N, for four weights across the window. The rectangle is the plain sum: 0.640% at two periods and flat in N, δ/2 as the earlier measurement found. The triangle is flat in N too but 75 times smaller at eight periods. The Hann window falls with N, as the −2.67 power: 414 ppm at two periods, 0.293 ppm at thirty-two. The four-term Blackman–Harris is below 4.85 ppm at every count from two. A weight that falls to zero at the window's ends counts the extra sliver of period at almost nothing.

The window that forgives the period

A converter that sums a waveform's square over whole periods reads its RMS exactly, and one that sums over periods 1.3% too long reads a sine 0.6% wrong — δ/2, for any number of periods — because the extra sliver of period counts at full weight. Weight the window down to zero at its ends and the sliver barely counts. Over eight periods a triangular weight reads the same sine 79 ppm wrong and a Hann weight 23 ppm; and they are different kinds of cure. The triangle is the only one that changes the error's order, from first to second in δ, so it wins when the period is nearly right; the Hann weight keeps first order but falls with the number of periods, about as its inverse square, so it wins over long windows. Both cost nothing with the period exact — from two periods up. Over one, a Blackman–Harris weight reads even a sine 10% wrong. The price is noise: a Hann-weighted reading of noise scatters √1.5 as widely.

Cancelling 50% of the line's reactance: a 0.3 lagging load's regulation goes from 7.78% to 4.18%, a unity one's from 2.17% to 1.96%, a 0.7 leading one's from −3.78% to −1.26%. computed by solving, not by drawing, at 50 Hz: a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, its regulation against the load's power factor from 0.7 leading to 0.3 lagging, with no compensation (dashed) and with 50% of the line's reactance cancelled by a series capacitor (solid). The solve agrees with the voltage divider in closed form to 9e-10 of a per cent. At 0.3 lagging the regulation falls from 7.781% to 4.176%; at 0.9 lagging, from 5.168% to 3.381%; at unity, only from 2.171% to 1.960%; and at 0.7 leading the far end, above the source at −3.778%, comes down to −1.255%. The capacitor cancels what the load's reactive current does in the line's reactance, in either direction, and pulls every load towards the regulation the line's resistance alone would give.

The drop a series capacitor can reach

A series capacitor cancels part of a line's reactance, so it can only cancel the part of the drop that the reactance makes — and that part is set by the load, not the line. On a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, half compensation takes a 0.3 lagging load from 7.78% regulation to 4.18% and a unity load only from 2.17% to 1.96%, and it brings a 0.71 leading load's raised far end back down. Cancel all of it and a leading load and its lagging twin sit at exactly the same voltage. Cancel more and the far end rises with its load; at exactly 100% the resonance is the fundamental and a far-end fault draws 4,600 A. Where the capacitor goes, the load cannot tell.

Two 230 V sources joined by 0.05 + j0.2 Ω: the most that can be received is 194 kW, at 76.0°; with 50% of the reactance cancelled it is 262 kW, at 63.4°. computed by solving, not by drawing, at 50 Hz: two 230 V sources, the sending one leading the receiving one by an angle δ, joined by a line of 0.05 Ω and j0.2 Ω with a series capacitor cancelling a fraction of the reactance; the real power absorbed at the receiving end against δ. Uncompensated (dashed) the maximum is 194.37 kW at 75.96°, the line's impedance angle. With 50% cancelled (solid) it is 261.55 kW at 63.43°. Both maxima match V² cos β (1 − cos β)/R, found by a search on the solve to a part in a million. Past its maximum the received power falls as the angle grows: a larger angle drives more current, and past the impedance angle the extra current's loss outgrows what it carries.

Sixty degrees, and the limit compensation stops raising

Series capacitors are put in transmission lines to raise how much power can pass between two sources before the angle between them runs out. The lossless textbook limit, V²/X(1 − k), rises without bound as the reactance is cancelled. With the line's resistance kept, the limit is V² cos β (1 − cos β)/R for an impedance angle β, and it peaks where β is exactly sixty degrees: 56.7 per cent cancellation and 264.5 kW on a 230 V tie of 0.05 + j0.2 Ω, against 194.4 uncompensated — then falls, to nothing at full cancellation. A line of R/X 0.1 can nearly triple its limit; one above 1/√3 cannot raise it at all. And at the best compensation the line delivers exactly half of what it is sent.

Over ±25% of the centre, three elements deliver 97.3% at worst; Bode and Fano allow 99.8%. computed by solving, not by drawing. The fraction of the available power a source of 2 times its resistance in inductive reactance delivers to a resistive load through the best matching network of 0, 1, 2 and 3 reactive elements for a band of ±25 per cent about the centre, each network the one whose worst transfer in the band is largest; the vertical lines mark the band. The worst in-band transfer is 54.2%, 82.8%, 89.5%, 97.3%; the Bode–Fano limit for any lossless network, reached only with infinitely many elements, is 99.81%.

What each element buys against the limit

A source whose resistance sits behind twice as much inductive reactance can deliver, over ±25 per cent of its centre frequency, 54.2 per cent of its available power to the best plain resistor and at worst 82.8 per cent through the best single capacitor. That single-element answer is exactly the fixed load for an uncertain reactance: the capacitor makes the reactance swing ±1 across the band and the load is √2 times the source. Two elements lift the worst case to 89.5, three to 97.3, and a fourth, in a chain of single elements, to 97.4. Bode and Fano bound every lossless network at 99.81 per cent over that band — a limit three elements come within a tenth of a decibel of and no finite network reaches.

With 0.05 Ω of machine reactance at each end the sixty-degree peak needs 107% of the line cancelled — out of reach — so the limit rises all the way to full cancellation, 261.6 kW against 145.3. computed by solving, not by drawing, at 50 Hz, searched over the angle between the two EMFs on the solve (dots) and from V²·cos β·(1 − cos β)/R with the totals in it (line): the 230 V tie of 0.05 + j0.2 Ω with each source a machine whose EMF is held behind 0.05 Ω of its own reactance, against the fraction of the LINE's reactance cancelled. The capacitor cannot reach the machines' reactance, so the total impedance angle reaches sixty degrees only at k* = (X + 2Xₘ − √3·R)/X = 106.7%, beyond full cancellation; the limit rises from 145.34 to 261.55 kW and never turns. Dashed: the bare tie, peaking at 56.7%. The slider is the machines' reactance.

The reactance the capacitor cannot reach

A series capacitor raises a tie's transfer limit until the loop's impedance angle is sixty degrees, and on a bare 0.05 + j0.2 Ω line that is 56.7% cancellation. Put a machine at each end, its EMF held behind a reactance of its own, and the capacitor still cancels only the line: the sixty degrees now needs the line's reactance plus twice a machine's, less √3 times the resistance, as a fraction of the line's reactance, which passes 100% as soon as each machine's reactance exceeds √3/2 of the line's resistance — 0.043 Ω here. Beyond that the limit rises at every step to full cancellation, and the lossless estimate of the gain, wildly high on a bare line, becomes nearly right: 1.43 against 1.50 at 0.2 Ω. The higher limit is reached with the receiving terminal lower — 180 V falling to 148 at 0.1 Ω — and the capacitor's own resistance is negligible for any power capacitor: a Q of 222 keeps the peak within 1%.

With the receiving end at 0.9 of the sending voltage the limit peaks at 62.6% cancellation, where the impedance angle is 56.3° — and the peak is still Vₛ²/4R = 264.5 kW. computed by solving, not by drawing, at 50 Hz, searched over the angle between the sources on the solve (dots) and from (Vᵣ·cos β/R)·(Vₛ − Vᵣ·cos β) (line): the 0.05 + j0.2 Ω tie with the sending source at 230 V and the receiving one at 207 V, against the fraction of the reactance cancelled; dashed, equal ends. The limit is a parabola in cos β with its top at cos β = Vₛ/(2Vᵣ) = 0.5556, an impedance angle of 56.25°, reached at k = 62.58%; its height there is Vₛ²/4R = 264.50 kW, the same as for equal ends. Uncompensated, this tie carries 180.53 kW at most. The slider is the receiving voltage as a fraction of the sending.

The peak a sagging receiver keeps

The sixty degrees at which series compensation stops raising a tie's transfer limit is a statement about two ends at equal voltage. With the receiving end lower, the limit is a parabola in the cosine of the impedance angle whose top is at cos β = Vₛ/2Vᵣ: 56.3° and 62.6% cancellation for a receiver at 0.9 of the sender, 33.6° and 83.4% at 0.6, full cancellation at one half. But the height of that top is Vₛ²/4R whatever the receiving voltage — 264.5 kW for the 0.05 + j0.2 Ω tie from a receiver at 1.1 of the sender down to one at 0.5 — and at it the receiving end takes exactly half of what is sent, to four decimal places, for every receiving voltage tried. The best compensated tie is the sending source driving a matched load, and the receiving source's voltage only decides how much capacitor that takes.

A capacitor of 67% of the load's reactive power, moved along a feeder whose load is spread evenly over 10 km. computed by solving, not by drawing at each of 30 positions: one phase of an 11 kV feeder of 0.3 + j0.35 Ω/km, carrying 2 MW at 0.8 lagging spread over 30 equal loads. Uncorrected it loses 16.8 kW a phase; with every load corrected to unity at its own terminals, 11.1 kW — so 5.66 kW is the reactive current's share. This capacitor does best at 67% of the way out, where the loss is 11.8 kW and 87.6% of the reactive share is gone. At the substation end it removes nothing; at the far end it overshoots.

The capacitor two-thirds of the way out

A feeder's reactive current costs loss in every section it passes through, and on a feeder whose load is spread along its length that current is largest at the substation and falls to nothing at the far end. Correcting it at the substation removes no loss at all. One phase of an 11 kV feeder carrying 2 MW at 0.8 lagging over ten kilometres loses 16.8 kW, of which 5.66 kW is the reactive current's; the best single capacitor is about two-thirds of the load's reactive power placed about two-thirds of the way out, and it removes 87.6% of that share — against the eight-ninths the textbook rule gives for an idealised line. Two capacitors at 2/5 and 4/5 remove 95.6%. The same capacitor left in at light load costs more than it saves below half load, and the rule for a continuous load is a statement about many taps.

A 230 V transformer's primary switched on at 0° of the mains, secondary open. computed by solving, not by drawing, marched with the core's saturating flux law and checked at the voltage zero against the netlist march. Settled, the primary draws a magnetising current of 111 mA peak. Switched on at 0° it draws 87.6 A in the first three cycles — 791 times the settled peak. At the voltage zero the first peak is 87.6 A, 791 times; at the voltage peak there is no inrush at all.

The instant a transformer is worst at

A capacitor-input rectifier draws its worst inrush when it is switched on at the peak of the mains. A transformer's own magnetising branch is the other way round: switched on at the voltage zero, a 230 V primary worked at 1.4 T draws 87.6 A in its first half-cycle, 791 times its settled magnetising current, and at the voltage peak it draws nothing extra at all. The core's flux has to start from zero, the voltage does not, and how close the working flux sits to half of saturation decides the size.

The second harmonic in each cycle of a transformer's inrush, as a share of the fundamental. computed by solving, not by drawing, the harmonics taken per cycle of the marched current. The first cycle carries 79% second harmonic and the second 93%. The share falls below the 15% a differential relay is commonly set to restrain at only in cycle 30, when the peak is 205 mA against a first peak of 88 A — the harmonic outlasts the inrush it identifies.

The harmonic that names an inrush

A transformer's differential relay sees an inrush as current going in and nothing coming out, which is what an internal fault looks like, and it tells them apart by the second harmonic. Marched cycle by cycle, an inrush starts at 79% second harmonic and stays above the usual 15% restraint for thirty cycles — long after its current has fallen from 88 A to 205 mA, because the current unwinds in a few cycles and the flux offset under it takes seconds. A fault's offset is a smooth exponential and peaks at 14.6% only when X/R is as low as three.

The harmonics of one phase of three balanced rectifier loads conducting 60°, each sorted into the sequence its three phasors form. computed by solving, not by drawing: each harmonic of the three phases decomposed into zero, positive and negative sequence. Every one is a single sequence to the arithmetic's floor: h1 positive, h3 zero, h5 negative, h7 positive, h9 zero, h11 negative, h13 positive, h15 zero. A balanced set shifts harmonic h by h × 120° between phases, so the third and its multiples are not shifted at all — zero sequence — the seventh is shifted as the fundamental is, and the fifth the other way round. Relative to the fundamental, the zero-sequence harmonics together are 72.5%, the negative 24.1% and the positive 16.7%.

The sequence a harmonic belongs to

Symmetrical components are defined on phasors, so they describe one frequency, and a rectifier load's current has many. Taken harmonic by harmonic, three balanced loads give a single sequence at every harmonic, to the arithmetic's floor: the third and its multiples zero sequence, the seventh, thirteenth and nineteenth positive, the fifth, eleventh and seventeenth negative — because harmonic h is shifted h × 120° between phases. The sequence decides where each harmonic can go. Connected line to line, the loads put no triplen in a line at all: 3.32 A of them circulates round the delta and never leaves it. Fed through a delta–wye transformer beside a second group, the fifth and seventh cancel in the supply and the eleventh and thirteenth remain, because the transformer turns the two sequences opposite ways.

The bank's impedance peaks at 0.966 Ω at 7.12 MHz; a one-ampere load step moves the supply by 132.4 mV. computed by solving, not by drawing. The bulk-and-ceramic pair of the decoupling essays — 10 µF with 5 mΩ and 5 nH, 100 nF with 30 mΩ and 1 nH — standing on a regulator of 2 mΩ and 20 nH, and the voltage at the bank when the load's current steps by one ampere, from the impedance's own step response by residues (solid). The impedance this bank presents peaks at 0.966 Ω at 7.12 MHz (upper line), the parallel resonance of the bulk part's inductance with the ceramic. The step rings at that frequency and its largest swing is 132.4 mV, 31.3 ns after the step — about a quarter period — which is 14% of the peak and 59% of the resonance's characteristic impedance √(L/C) = 0.224 Ω (lower line).

The peak a load step does not see

A decoupling bank is specified by its impedance against frequency, and the number that fails a target is the anti-resonance peak — 0.966 Ω at 7.12 MHz for the bulk-and-ceramic pair standing on a regulator. A load that steps by one ampere moves that supply by 132 mV, 14% of what the peak suggests: a step rings the resonance once, and its first swing is set by the resonance's characteristic impedance √(L/C) = 0.224 Ω, not by its Q. The peak is the voltage per ampere of a load that sits at the resonance; switched at 7.12 MHz the same load builds over six cycles to ±611 mV, the peak times the current's fundamental. So damping, the cure for the peak, is a cure for that load only: sixteen times the ESR cuts the peak 8.9-fold and leaves a step's swing between 120 and 155 mV. What decides a step is its edge — 132 mV for anything faster than a few nanoseconds, 28 mV for a microsecond.

Asked for 105% of the nose power, a tap changer that blocks on a wrong-signed step stops at 9.759 V and holds it; one that does not keeps raising, and the voltage keeps falling. Marched. The 10 V source behind 1 Ω of the regulator essays, its load drawing 105% of the line's 25 W nose power at the 10 V setpoint, regulated by a tap changer that raises the ratio by 1.25% every 5 s while the load is more than 20 mV low. With no blocking rule (dashed) it climbs past the nose ratio √(Rₗ/R) = 1.9518 and keeps going, to n = 3.250 and 8.61 V by 900 s, still falling; the integrating regulator of the earlier essay (dotted) collapses the same way, faster. With the rule (solid) the tap at n = 1.9625 is the first to lower the voltage, the regulator stops at 385 s, and the load holds 9.759 V — within a tap of the most this line can give it, 9.759 V. The setpoint is out of reach either way; the rule converts a collapse into a stall.

The rule that reads the sign of the gain

A regulator that raises a ratio whenever its load is low collapses the voltage once the load asks for more than the line's nose power, because past the nose raising the ratio lowers the voltage. The standard protection is a rule: after each tap, compare the voltage with the one before, and if it fell, stop. On a 10 V line asked for 105% of its 25 W, a 1.25% tap changer with the rule stops at n = 1.9625, the first tap past the nose, and holds 9.759 V — the most the line can give — where without it the ratio climbs to 3.25 and the voltage is 8.61 V and still falling. The rule is exact without noise and fragile with it, because it reads a difference that vanishes at the nose: with 3 mV of measurement noise it wrongly stops a raise that could have reached the setpoint 0.3% of the time at 98% of the nose and 15% at 99.5%. Trusting it to 1% costs margin — 97.9% of the nose at 3 mV, 79.9% at 10 mV — or coarser taps.

A 640 kvar bank on a 16 MVA 400 V bus: alone its resonance with the supply is at h = 5.00, and with a 7% reactor in series at 3.01, with the bank's own null at 3.78 between that and everything above it. computed by solving, not by drawing: the impedance per phase at a 400 V bus, with a short-circuit level of 16 MVA and a 640 kvar correction bank, against harmonic order, in closed form and at the fifth by a netlist. The bank alone (dashed) resonates with the supply at h = 5.00, where the bus impedance peaks. With a reactor of 7% of the capacitor's fundamental reactance in series (solid), the bank's own series resonance is at h = 1/√0.07 = 3.78, a deep null, and the parallel peak has moved down to h = 3.01. Above the null the bank is an inductor, in parallel with the supply's inductance, so there is nothing for any higher harmonic to resonate with.

The reactor that keeps a bank out of it

A correction bank on a stiff bus resonates with the supply at a harmonic set by the two sizes, and at 640 kvar on 16 MVA that harmonic is the fifth, which it multiplies by 34. A reactor of 7 per cent of the capacitor's reactance in series puts a null at h = 3.78, and above that null the bank is an inductor, in parallel with another inductor, with nothing left to resonate. So the fifth is never raised at any size of bank. It was not free. The capacitor now stands 7.5 per cent above the bus, the resonance has gone below the null and can land on the third, 22.7 times at 654 kvar, and the number that looks like a detail, 7 rather than the 4 that would tune the bank to the fifth, is what keeps an ageing bank on the right side of its null.

All essays