Voltage regulation — where it appears
Named by 11 essays across one field — each of them below, with the objects they name alongside it.
The far end that rises
Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.
The reactance cancelled, and the resonance it buys
Putting a capacitor in series with a feeder cancels part of its reactance and the far end falls less: five per cent of regulation becomes four and a quarter at a quarter compensation and 2.7 per cent at seventy per cent. What comes with it is a series resonance that was not there before, at the line frequency times the root of the fraction cancelled — so a quarter compensation resonates at exactly half the line frequency and a ninth at exactly a third. The line's own inductance is not in that answer and neither is the voltage.
The load that has two voltages or none
A load that takes a fixed power takes more current as its voltage falls, and on a line with impedance in it every power below a limit is delivered at two voltages and every power above it at none. The limit sits at the load the maximum-power theorem describes, half the source voltage on a resistive line. On fifty ohms and a hundred of reactance a load leading by sixty degrees reaches that limit with its far end at 1.055 of the source, and at nine tenths of it reads 1.172 — so a far end that reads high is not a far end with margin. On a direct-current bus the lower of the two voltages is not a state at all: one per cent below it the bus runs down to nothing in 3.48 milliseconds.
The headroom that is the line's own charge
A line of 50 + j100 ohms delivers at most 0.6180 of a matched resistive line's power to a unity-power-factor load, with 0.5878 of the source voltage left. Give the line its own shunt capacitance — a π, half at each end, B|Z| = 0.4 in all — and the nose moves to 0.7025 at 0.6895: 13.7 per cent more power and 17.3 per cent more voltage. It is headroom, but not the headroom the far end advertises, which with no load rises 21.1 per cent. The capacitance turns the source and line into a Thevenin equivalent with more voltage behind more impedance, and it moves a voltage threshold's meaning in opposite directions depending on whether it is referred to the source or to the unloaded far end.
The regulator that pushes past the nose
A regulator that raises a ratio whenever its load's voltage is low is a stabiliser only while raising the ratio raises the voltage, and on a line that stops being true at exactly the nose: the load's voltage, n·V₀ times the load resistance over n²R plus that resistance, peaks at a turns ratio of the square root of the load over the line and falls beyond it. Ask the load for 90 per cent of the nose power and the regulator settles at n = 1.519 — unless it starts above n = 2.925, where the same setpoint is met on the wrong side of the peak, and then it collapses the voltage. Ask for 101 per cent and the voltage climbs to 9.950 volts, the most the line allows, and is below half its setpoint 256 seconds later. Near the nose the collapse takes a time that grows as the inverse square root of the excess: 2,521 seconds at a hundredth of a per cent.
The drop a series capacitor can reach
A series capacitor cancels part of a line's reactance, so it can only cancel the part of the drop that the reactance makes — and that part is set by the load, not the line. On a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, half compensation takes a 0.3 lagging load from 7.78% regulation to 4.18% and a unity load only from 2.17% to 1.96%, and it brings a 0.71 leading load's raised far end back down. Cancel all of it and a leading load and its lagging twin sit at exactly the same voltage. Cancel more and the far end rises with its load; at exactly 100% the resonance is the fundamental and a far-end fault draws 4,600 A. Where the capacitor goes, the load cannot tell.
Sixty degrees, and the limit compensation stops raising
Series capacitors are put in transmission lines to raise how much power can pass between two sources before the angle between them runs out. The lossless textbook limit, V²/X(1 − k), rises without bound as the reactance is cancelled. With the line's resistance kept, the limit is V² cos β (1 − cos β)/R for an impedance angle β, and it peaks where β is exactly sixty degrees: 56.7 per cent cancellation and 264.5 kW on a 230 V tie of 0.05 + j0.2 Ω, against 194.4 uncompensated — then falls, to nothing at full cancellation. A line of R/X 0.1 can nearly triple its limit; one above 1/√3 cannot raise it at all. And at the best compensation the line delivers exactly half of what it is sent.
The reactance the capacitor cannot reach
A series capacitor raises a tie's transfer limit until the loop's impedance angle is sixty degrees, and on a bare 0.05 + j0.2 Ω line that is 56.7% cancellation. Put a machine at each end, its EMF held behind a reactance of its own, and the capacitor still cancels only the line: the sixty degrees now needs the line's reactance plus twice a machine's, less √3 times the resistance, as a fraction of the line's reactance, which passes 100% as soon as each machine's reactance exceeds √3/2 of the line's resistance — 0.043 Ω here. Beyond that the limit rises at every step to full cancellation, and the lossless estimate of the gain, wildly high on a bare line, becomes nearly right: 1.43 against 1.50 at 0.2 Ω. The higher limit is reached with the receiving terminal lower — 180 V falling to 148 at 0.1 Ω — and the capacitor's own resistance is negligible for any power capacitor: a Q of 222 keeps the peak within 1%.
The peak a sagging receiver keeps
The sixty degrees at which series compensation stops raising a tie's transfer limit is a statement about two ends at equal voltage. With the receiving end lower, the limit is a parabola in the cosine of the impedance angle whose top is at cos β = Vₛ/2Vᵣ: 56.3° and 62.6% cancellation for a receiver at 0.9 of the sender, 33.6° and 83.4% at 0.6, full cancellation at one half. But the height of that top is Vₛ²/4R whatever the receiving voltage — 264.5 kW for the 0.05 + j0.2 Ω tie from a receiver at 1.1 of the sender down to one at 0.5 — and at it the receiving end takes exactly half of what is sent, to four decimal places, for every receiving voltage tried. The best compensated tie is the sending source driving a matched load, and the receiving source's voltage only decides how much capacitor that takes.
The capacitor two-thirds of the way out
A feeder's reactive current costs loss in every section it passes through, and on a feeder whose load is spread along its length that current is largest at the substation and falls to nothing at the far end. Correcting it at the substation removes no loss at all. One phase of an 11 kV feeder carrying 2 MW at 0.8 lagging over ten kilometres loses 16.8 kW, of which 5.66 kW is the reactive current's; the best single capacitor is about two-thirds of the load's reactive power placed about two-thirds of the way out, and it removes 87.6% of that share — against the eight-ninths the textbook rule gives for an idealised line. Two capacitors at 2/5 and 4/5 remove 95.6%. The same capacitor left in at light load costs more than it saves below half load, and the rule for a continuous load is a statement about many taps.
The rule that reads the sign of the gain
A regulator that raises a ratio whenever its load is low collapses the voltage once the load asks for more than the line's nose power, because past the nose raising the ratio lowers the voltage. The standard protection is a rule: after each tap, compare the voltage with the one before, and if it fell, stop. On a 10 V line asked for 105% of its 25 W, a 1.25% tap changer with the rule stops at n = 1.9625, the first tap past the nose, and holds 9.759 V — the most the line can give — where without it the ratio climbs to 3.25 and the voltage is 8.61 V and still falling. The rule is exact without noise and fragile with it, because it reads a difference that vanishes at the nose: with 3 mV of measurement noise it wrongly stops a raise that could have reached the setpoint 0.3% of the time at 98% of the nose and 15% at 99.5%. Trusting it to 1% costs margin — 97.9% of the nose at 3 mV, 79.9% at 10 mV — or coarser taps.
Named alongside it
The objects these essays reach for when they reach for this one.
Maximum power transferDesign tradeoffReactive powerPhasorPower factorReactanceLine impedanceModel rangeReal powerOperating pointResonanceSeries resonance