The extent to which the three phases of a supply or of the load on it differ from one another. It produces a zero-sequence current, which the neutral carries, and a negative-sequence current, which the neutral cannot see; the two are equal in size while a neutral is present and all of it is negative sequence once the neutral is removed.

Named by 3 essays across 2 fields — each of them below, with the objects they name alongside it.

The neutral of a three-phase supply with one phase 30% off. computed by solving, not by drawing. Balanced, the three line currents sum to 4.6e-16 of one of them and the neutral carries nothing. With one phase 30% heavier the neutral carries 2.65 A against a line current of 11.50 A. The neutral reaches a tenth of a line current at 11.1% imbalance.

Three phases, and the wire that carries nothing

Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.

power · Three-phase
Two of the four errors are divided by the gain; the best the instrument gets is 110.1 dB, at ×776. computed by solving, not by drawing. The four mechanisms that limit a three-amplifier instrumentation amplifier's common-mode rejection, each measured alone against the gain of its input stage and then all four together, at 50.0 Hz with 1 kΩ of imbalance between the source resistances and 10 pF at each input. The difference stage's four resistors and the difference amplifier's own rejection are injected after the gain, so their common-mode gain is a constant — 1.998 mV/V and 0.0100 mV/V — and the rejection they allow rises decibel for decibel with the gain. The input pair's mismatch and the source's time-constant gap are injected before it, so they are amplified by exactly the gain the signal is and the rejection they allow is flat. The four add as complex numbers: the two largest are real and of opposite sign, they cancel at a gain of 776, and what is left there is the source's 3.142 µV/V, which is purely imaginary because it is ωΔτ. The instrument's best is 110.07 dB against the source's own 110.06, and above that gain more of it buys nothing.

The errors that arrive before the gain

Four earlier measurements each found a different owner of one instrument's common-mode rejection and each measured it alone. Solved together, the four are complex numbers that add — to 1.25 parts in ten thousand — and two of them carry a factor of the first stage's gain while two do not. The two that do cancel the two that do not at a gain of 776, and what is left there is 110.066 decibels, which is exactly the number the cable sets. Better-matched amplifiers move that gain from 93 to 3392 and do not move the ceiling by a hundredth of a decibel.

instruments · Common-mode rejection
The two sequences a neutral current says nothing about. computed by solving, not by drawing at 61 imbalances. Three 20 Ω loads on a 230 V, 50 Hz star supply, one of them raised by a fraction of itself, with the neutral in place. The zero-sequence current is the one the neutral carries three times and is the only one this collection has read; the negative sequence is a balanced set of three phasors rotating the other way. At 30.0 per cent imbalance it is 0.8846 A against 10.6154 A of positive sequence, 8.333 per cent, against 8.333 per cent from x/(3 + 2x). Two per cent arrives at 6.250 per cent imbalance, bisected on the network.

The half the neutral does not carry

A star load unbalanced in one phase produces two things, not one. The neutral carries three times the zero-sequence current, which is the half this collection has read; the other half is a negative-sequence set of exactly the same size, rotating backwards, that the neutral never sees. With 0.5 Ω of line in front of 20 Ω loads, losing a phase entirely puts 50.00 per cent negative sequence in the current and 0.8265 per cent in the voltage a switchboard meter reads.

power · Three-phase

Named alongside it

The objects these essays reach for when they reach for this one.

Neutral currentSuperpositionSymmetrical componentsThree-phaseCommon-mode rejectionComponent toleranceDesign tradeoffInstrumentation amplifierLine impedanceLine lossMeasurement conditionModel range