Symmetrical components — where it appears
Named by 2 essays across one field — each of them below, with the objects they name alongside it.
Three phases, and the wire that carries nothing
Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.
The half the neutral does not carry
A star load unbalanced in one phase produces two things, not one. The neutral carries three times the zero-sequence current, which is the half this collection has read; the other half is a negative-sequence set of exactly the same size, rotating backwards, that the neutral never sees. With 0.5 Ω of line in front of 20 Ω loads, losing a phase entirely puts 50.00 per cent negative sequence in the current and 0.8265 per cent in the voltage a switchboard meter reads.
Named alongside it
The objects these essays reach for when they reach for this one.
ImbalanceNeutral currentThree-phaseLine impedanceLine lossMeasurement conditionSuperpositionTriplen harmonicsVerification