Superposition — where it appears
Named by 11 essays across 7 fields — each of them below, with the objects they name alongside it.
The step that is too big
A linear circuit scales — double the input and the output doubles, exactly. A real amplifier does not, because its output can only move at a fixed rate, and the amplitude at which the two stop agreeing is about eighty millivolts for an ordinary part. No transfer function contains that number, because no transfer function can.
Two solves that add, and the one that does not
Every node voltage and every branch current in a linear network is the sum of the per-source solves, here to the last bit of a double at eighty-one settings. The power is not, and the gap is not a correction: two equal sources in antiphase put nothing at all into a load while adding their powers gives 222 milliwatts, and the sum is within one per cent of the truth only when one source is two hundred times the other.
The resistor the noise comes from
Two identical 1.59 kΩ resistors in one third-order filter contribute 60.0 and 40.0 per cent of its output noise, because a resistor's noise is filtered by everything after it and by nothing before it. Solved one resistor at a time, the rule everybody carries — the resistance in the noise bandwidth — comes out 1.551 times the truth on a seventh-order Chebyshev and 0.791 times on a sixth-order Bessel. It is wrong in both directions on the same axis, so no factor repairs it.
Where an open switch leaks to
A lone switch has a band whose width no load can change, because its open state leaks into the load. In a multiplexer the seven open channels leak into a node the selected channel holds, so the load leaves the answer and the source takes its place: one per cent of leak at 91.0 megahertz from buffered sources and 901 kilohertz from fifty ohms, moving as the first power of the tolerance rather than the second. Adding the channels' capacitance into one forty-picofarad switch puts it at 804 kilohertz, near the fifty-ohm figure by coincidence and a hundred and thirteen times low for a buffered one.
The ripple that arrives as a comb
The rejection essay multiplied two numbers: 1.331 volts of reservoir ripple and the regulator's 36.0 decibels of rejection at a hundred hertz, for 21 millivolts at the output. The ripple is a sawtooth, a comb of lines at every multiple of a hundred hertz, and the rejection worsens at twenty decibels a decade — so the second line arrives at nearly the size of the first, and the third too. Summed with their phases, the output is 60.62 millivolts, 2.87 times the estimate, and the hundred-hertz line carries only 23.4 per cent of it. A reservoir twenty-one times larger cuts the rail's ripple 14.8 times and the regulated ripple 5.95.
The errors that arrive before the gain
Four earlier measurements each found a different owner of one instrument's common-mode rejection and each measured it alone. Solved together, the four are complex numbers that add — to 1.25 parts in ten thousand — and two of them carry a factor of the first stage's gain while two do not. The two that do cancel the two that do not at a gain of 776, and what is left there is 110.066 decibels, which is exactly the number the cable sets. Better-matched amplifiers move that gain from 93 to 3392 and do not move the ceiling by a hundredth of a decibel.
The half the neutral does not carry
A star load unbalanced in one phase produces two things, not one. The neutral carries three times the zero-sequence current, which is the half a neutral ammeter reads; the other half is a negative-sequence set of exactly the same size, rotating backwards, that the neutral never sees. With 0.5 Ω of line in front of 20 Ω loads, losing a phase entirely puts 50.00 per cent negative sequence in the current and 0.8265 per cent in the voltage a switchboard meter reads.
The peak that only has a bound
Power does not superpose and the gap has a closed form — two times the real part of one current times the conjugate of the other, exact at every setting. A peak has nothing of the kind. A ten-volt fundamental with a third harmonic a third its size has one root-mean-square value, 7.454 volts at every relative phase because the two are orthogonal, and a peak running from 9.428 to 13.333 volts across the same sweep — reaching the sum of the two peaks exactly at 180 degrees, where the harmonic's own crest lands on the fundamental's, and having no closed form at all at the other end.
The source that must not be zeroed
Superposition says to zero all the sources but one, and the care usually taken over that instruction is that zeroing is not deleting — a voltage source with no voltage is a short circuit and it stays in the netlist. A dependent source needs the opposite care: it must not be zeroed at all, because it is an element whose law involves another node rather than a source the theorem is about. Zeroed, it is a short circuit, and the answer that comes back is 4.0625 volts at every gain from one to three hundred — while the true answer moves from 3.82 volts to 0.206.
The cross terms that outnumber the sources
With two sources the power in a load has one cross term, and adding the separate powers is wrong by a factor of two. With thirty-two there are four hundred and ninety-six of them, and the factor is thirty-two: 940 milliwatts delivered against the 29.4 that adding gives. With the same thirty-two sources at seeded random phases it is 26.9 milliwatts — the sum itself, inside the standard error of sixty-four runs, because every cross term averages to nothing. One identity, two limits, and the two are a phased array's gain and a noise sum's.
How many sources the cross terms count
N equal coherent sources on one load deliver N times the sum of their separate powers. Sources of unequal size deliver (Σ|a|)²/Σa² times it — solved on the network to ten figures — which is the number of equal sources that would carry the same penalty: a participation ratio. Amplitudes falling by 0.8 a source cap it at (1 + q)/(1 − q) = 9 however many there are; one large source and thirty-one at a tenth of its amplitude give 12.8, not 32, and for small sources the excess is 2(N − 1)ε — their amplitudes, not their powers, so thirty-one sources carrying a hundredth of the large one's power each turn 1.31 times its power into 16.8 times it when they line up. Random amplitudes take a fixed fraction off the count, (mean)²/(mean square): 0.75 for uniform ones. And with random phases none of it matters: the load takes the sum.
Named alongside it
The objects these essays reach for when they reach for this one.
Model rangeVerificationDesign tradeoffQuadratureReal powerImbalanceLoop gainMeasurement conditionModified nodal analysisNonlinearitySource impedanceCoherence