Reactive power — where it appears
Named by 10 essays across one field — each of them below, with the objects they name alongside it.
The current that does no work
A solved network has been reporting its own real power on every page of this collection, as the second of the two checks each answer passes before it is drawn. What that check discards is the imaginary half — the power that flows out to a reactance and back again, does nothing, and is still carried by the cable, still heats the transformer, and is still on the bill.
The load that takes the most
A load equal to the source resistance takes more power than any other, and it does so at exactly fifty per cent efficiency — the source burns as much as the load receives. Ninety per cent efficiency needs a load nine times the source and delivers 36% of what was available, and a load half the source resistance delivers exactly as much as one twice it.
The far end that rises
Voltage regulation is quoted as a percentage: how far the voltage at the end of a line falls when the load is applied. The percentage carries neither of the two things that decide it. Past a computable angle of leading load the voltage at the far end goes above the source's — 28.35 degrees for a line of fifty ohms and a hundred of reactance — and with no reactance in the line there is no such angle at all, because the rise is a partial resonance and needs both halves.
The reactance cancelled, and the resonance it buys
Putting a capacitor in series with a feeder cancels part of its reactance and the far end falls less: five per cent of regulation becomes four and a quarter at a quarter compensation and 2.7 per cent at seventy per cent. What comes with it is a series resonance that was not there before, at the line frequency times the root of the fraction cancelled — so a quarter compensation resonates at exactly half the line frequency and a ninth at exactly a third. The line's own inductance is not in that answer and neither is the voltage.
The energy a unity power factor doubles
Reactive power can be computed three ways, and their agreement is easily called a verification. Two of the three are one theorem written twice and cannot disagree about anything; only the third is independent, and what it computes is a difference. Correcting a 20 Ω, 50 mH load to a power factor of 1.000000 takes its reactive power from 1,285 var to nothing and takes the energy stored in the installation from 2,044.9 mJ to 4,089.7 mJ — exactly twice, at every load and every frequency.
The load that has two voltages or none
A load that takes a fixed power takes more current as its voltage falls, and on a line with impedance in it every power below a limit is delivered at two voltages and every power above it at none. The limit sits at the load the maximum-power theorem describes, half the source voltage on a resistive line. On fifty ohms and a hundred of reactance a load leading by sixty degrees reaches that limit with its far end at 1.055 of the source, and at nine tenths of it reads 1.172 — so a far end that reads high is not a far end with margin. On a direct-current bus the lower of the two voltages is not a state at all: one per cent below it the bus runs down to nothing in 3.48 milliseconds.
The load that may be complex
Freed of the constraint that it be a resistance, the best load is the source's conjugate — found here by a two-dimensional search on the solved network rather than assumed — and it takes the available power at exactly fifty per cent efficiency whatever the source's reactance. A load that may only be a resistance takes 2/(1 + √(1+x²)) of that, and at a source reactance of twice its resistance that is exactly the golden ratio less one, 0.618034. The resistor-only load is also the MORE efficient of the two, rising towards one while the conjugate sits at a half for ever.
The headroom that is the line's own charge
A line of 50 + j100 ohms delivers at most 0.6180 of a matched resistive line's power to a unity-power-factor load, with 0.5878 of the source voltage left. Give the line its own shunt capacitance — a π, half at each end, B|Z| = 0.4 in all — and the nose moves to 0.7025 at 0.6895: 13.7 per cent more power and 17.3 per cent more voltage. It is headroom, but not the headroom the far end advertises, which with no load rises 21.1 per cent. The capacitance turns the source and line into a Thevenin equivalent with more voltage behind more impedance, and it moves a voltage threshold's meaning in opposite directions depending on whether it is referred to the source or to the unloaded far end.
The drop a series capacitor can reach
A series capacitor cancels part of a line's reactance, so it can only cancel the part of the drop that the reactance makes — and that part is set by the load, not the line. On a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, half compensation takes a 0.3 lagging load from 7.78% regulation to 4.18% and a unity load only from 2.17% to 1.96%, and it brings a 0.71 leading load's raised far end back down. Cancel all of it and a leading load and its lagging twin sit at exactly the same voltage. Cancel more and the far end rises with its load; at exactly 100% the resonance is the fundamental and a far-end fault draws 4,600 A. Where the capacitor goes, the load cannot tell.
The capacitor two-thirds of the way out
A feeder's reactive current costs loss in every section it passes through, and on a feeder whose load is spread along its length that current is largest at the substation and falls to nothing at the far end. Correcting it at the substation removes no loss at all. One phase of an 11 kV feeder carrying 2 MW at 0.8 lagging over ten kilometres loses 16.8 kW, of which 5.66 kW is the reactive current's; the best single capacitor is about two-thirds of the load's reactive power placed about two-thirds of the way out, and it removes 87.6% of that share — against the eight-ninths the textbook rule gives for an idealised line. Two capacitors at 2/5 and 4/5 remove 95.6%. The same capacitor left in at light load costs more than it saves below half load, and the rule for a continuous load is a statement about many taps.
Named alongside it
The objects these essays reach for when they reach for this one.
Power factorVoltage regulationMaximum power transferDesign tradeoffLine impedanceReal powerSeries resonanceApparent powerComplex powerImpedance matchingInternal resistanceModel range