Triplen harmonics — where it appears
Named by 2 essays across one field — each of them below, with the objects they name alongside it.
Three phases, and the wire that carries nothing
Three sources a third of a cycle apart, feeding three equal loads, return a current of 5×10⁻¹⁵ amperes down the wire between the star points. That is zero, and the whole of three-phase distribution rests on it. What is worth measuring is how fast it stops being zero, and the answer is that an eleven per cent imbalance in one phase puts a tenth of a line current down a conductor often sized on the assumption that it carries none.
The neutral that carries more than a line
Three balanced loads draw currents summing to 5.3 × 10⁻¹⁵ amperes in the neutral. That is a theorem about sinusoids, and it uses nothing except that each current is a single frequency. A harmonic of order three is shifted by 360° between phases, which is no shift at all — so the third harmonics add, and for any conduction angle narrow enough that the pulse trains stay disjoint the neutral carries exactly √3 times a line current.
Named alongside it
The objects these essays reach for when they reach for this one.
Neutral currentThree-phaseImbalanceModel rangePower factorSymmetrical componentsTotal harmonic distortion