Power, and the part that does no work

Sixty degrees, and the limit compensation stops raising

Series capacitors are put in transmission lines to raise how much power can pass between two sources before the angle between them runs out. The lossless textbook limit, V²/X(1 − k), rises without bound as the reactance is cancelled. With the line's resistance kept, the limit is V² cos β (1 − cos β)/R for an impedance angle β, and it peaks where β is exactly sixty degrees: 56.7 per cent cancellation and 264.5 kW on a 230 V tie of 0.05 + j0.2 Ω, against 194.4 uncompensated — then falls, to nothing at full cancellation. A line of R/X 0.1 can nearly triple its limit; one above 1/√3 cannot raise it at all. And at the best compensation the line delivers exactly half of what it is sent.

Assumes: The reactance cancelled, and the resonance it buys · The load that takes the most · Three voltages that close on one, and the steady state they assume

The drop a series capacitor can reach measured a series capacitor as a cure for voltage drop and found it reaching only the part of the drop the line’s reactance makes, with the resistance’s part left exactly where it was. On a distribution feeder that is the whole reason to fit one. On a transmission line it is the lesser reason. The greater one is transfer capability: two ends of a long line are each held at their voltage by the machines connected there, the power that flows between them is set by the angle between those voltages, and there is a largest power the line can carry before a larger angle carries less. Cancelling reactance raises that largest power, and the textbook says by how much: the limit is V2/XV^2/X, so cancelling a fraction kk multiplies it by 1/(1−k)1/(1-k).

That formula has no resistance in it, and the earlier essay found resistance to be the one thing a series capacitor cannot touch. With the resistance kept, the limit does not rise without bound. It rises, peaks at a definite compensation — the one that leaves the line’s impedance angle at sixty degrees — and falls, to nothing at full cancellation. This essay solves two sources and a compensated line directly and finds the peak, its position, what decides it, and a property of the line at its peak that is an old theorem arriving by a new road.

Two 230 V sources joined by 0.05 + j0.2 Ω: the most that can be received is 194 kW, at 76.0°; with 50% of the reactance cancelled it is 262 kW, at 63.4°computed by solving, not by drawing, at 50 Hz: two 230 V sources, the sending one leading the receiving one by an angle δ, joined by a line of 0.05 Ω and j0.2 Ω with a series capacitor cancelling a fraction of the reactance; the real power absorbed at the receiving end against δ. Uncompensated (dashed) the maximum is 194.37 kW at 75.96°, the line's impedance angle. With 50% cancelled (solid) it is 261.55 kW at 63.43°. Both maxima match V² cos β (1 − cos β)/R, found by a search on the solve to a part in a million. Past its maximum the received power falls as the angle grows: a larger angle drives more current, and past the impedance angle the extra current's loss outgrows what it carries.0100200300020406080100120angle between the two sources (degrees)power received (kW)line0.05 + j0.2 Ωcancelled50%limit, bare194.4 kW at 76.0°limit, now261.6 kW at 63.4°best cancellation56.7%solved, then checked — two sources, 81 angleslimit 262 kW at 63°
Fig. 1 The real power absorbed at the receiving end of a tie between two 230 V sources through 0.05 + j0.2 Ω, against the angle by which the sending source leads, uncompensated (dashed) and with a fraction of the line’s reactance cancelled (solid). The slider is the fraction; the dots are each curve’s maximum.

Two sources and a line

The circuit is the smallest one with the property: two ideal 230 V sources at 50 Hz, the receiving one at zero phase and the sending one leading it by an angle δ\delta, joined by the feeder of the earlier essays — 0.05 Ω of resistance and 0.2 Ω of reactance — with a series capacitor cancelling a fraction kk of the reactance. The line’s current is solved, and the real power absorbed by the receiving source is the product of its voltage and the conjugate of that current.

Uncompensated, the received power rises from zero as the angle opens, peaks at 194.37 kW at an angle of 75.96°, and falls after it. With half the reactance cancelled the curve is steeper and higher: its peak is 261.55 kW, at 63.43°. Both peaks sit at an angle equal to the line’s own impedance angle, β=arctan⁡(X/R)\beta = \arctan(X/R) — 75.96° for the bare line, 63.43° with half its reactance gone — and both match a closed form to a part in a million.

The closed form comes from the phasors. With the line’s impedance written as ∣Z∣∠β|Z|\angle\beta and both sources at magnitude VV, the power received is

Pr=V2∣Z∣[cos⁡(β−δ)−cos⁡β],P_r = \frac{V^2}{|Z|}\left[\cos(\beta - \delta) - \cos\beta\right],

which is largest at δ=β\delta = \beta, where it is V2(1−cos⁡β)/∣Z∣V^2(1 - \cos\beta)/|Z|. Since ∣Z∣=R/cos⁡β|Z| = R/\cos\beta, that is

Pmax=V2Rcos⁡β (1−cos⁡β).P_{max} = \frac{V^2}{R}\cos\beta\,(1 - \cos\beta).

The textbook’s lossless limit is the case R→0R \to 0, β→90°\beta \to 90°, where it becomes V2/XV^2/X. With any resistance at all it is a function of the impedance angle, and the angle is what a series capacitor changes.

The peak at sixty degrees

As the capacitor cancels more reactance, X(1−k)X(1-k) falls, the impedance angle falls from its bare value towards zero, and the limit follows cos⁡β(1−cos⁡β)\cos\beta(1 - \cos\beta) — a product that is zero at both ends and largest in between.

The transfer limit rises with compensation only until the line's impedance angle is sixty degrees — 56.7% cancelled, 264.5 kW against 194.4 — and falls to nothing at full cancellation. computed by solving, not by drawing, at 50 Hz: the largest power the receiving source of the 230 V tie can absorb, searched over the angle between the sources on the solve (dots) and from V² cos β (1 − cos β)/R (line), against the fraction of the line's reactance cancelled. It rises from 194.37 kW, peaks at 264.50 kW — V²/4R — where the cancellation leaves the impedance angle at exactly 60°, k = 1 − √3·R/X = 56.7%, and falls beyond it, to zero at full cancellation, where a purely resistive link cannot deliver power between two sources of equal voltage at all. The lossless textbook limit, V²/X(1 − k) (dashed), rises without bound and agrees with the solve only for the first few per cent.
Fig. 2 The largest power the receiving end can absorb, searched over the angle between the sources on the solve (dots) and from the closed form (line), against the fraction of the reactance cancelled, with the lossless limit V2/X(1−k)V^2/X(1 - k) dashed. The limit peaks at 56.7 per cent cancellation, where it is V2/4RV^2/4R = 264.5 kW.

The product c(1−c)c(1-c) is largest at c=12c = \tfrac12, so the limit is largest when cos⁡β=12\cos\beta = \tfrac12 — when the impedance angle is exactly sixty degrees. The compensation that puts it there is

k∗=1−3 RX,k^* = 1 - \sqrt3\,\frac{R}{X},

which for this line, with R/X=0.25R/X = 0.25, is 56.7 per cent, and the limit there is V2/4RV^2/4R = 264.50 kW, against 194.37 uncompensated: 36 per cent more power through the same line. The search on the solve finds 264.50 at 56.7 per cent to a part in a million, and finds no compensation that beats it.

Past the peak the limit falls. Beyond 78 per cent cancelled it is below its uncompensated value; at 90 per cent it is 36 per cent of it; and at full cancellation it is zero. A purely resistive link between two sources of equal voltage cannot deliver power to the receiving end at any angle, because any current it carries is driven by a difference between the two voltages, and with no reactance to rotate that current the receiving source always receives less than the line dissipates. The lossless formula, dashed in the figure, agrees with the solve for the first few per cent and then diverges without bound. It is not a slightly optimistic estimate of the limit; past a moderate compensation it is the wrong shape.

Why a resistance cannot carry it

The zero at full cancellation deserves a picture, because it is where the lossless intuition fails most completely. With two sources of equal magnitude, the voltage across the line is the chord between two points on a circle, and the current is that chord divided by the line’s impedance. A reactive line turns the current ninety degrees from the chord, which puts it nearly in phase with both sources’ voltages when the angle between them is small — so both ends see a current in phase with their own voltage, one sending and one receiving, and very little is lost between them. A resistive line leaves the current along the chord, which is perpendicular to the bisector of the two voltages; at the receiving end the current then has a component against the receiving voltage, and the receiving source is pushed to send rather than receive. Three voltages that close on one drew Kirchhoff’s law as a closed polygon of phasors; here the polygon is a triangle of two equal voltages and a line drop, and whether the receiving end gains power is a question of which way the drop’s current points.

Between the two extremes the line’s impedance angle sets how far the current is rotated, and sixty degrees is where the gain from rotation and the loss in the resistance balance in the receiving end’s favour most. It is a property of the angle alone — the same for a 230 V feeder and a 400 kV line — which is why the optimum is a formula in R/XR/X and nothing else.

The line decides how much there is to gain

The optimum depends on the line through one number, its ratio of resistance to reactance, and so does the gain.

How much compensation can raise a line's limit is set by its R/X: 0.05: ×5.27 at 91%, 0.1: ×2.79 at 83%, 0.25: ×1.36 at 57%, 0.5: ×1.01 at 13%, 0.7: nothing. computed by solving, not by drawing: the closed form V² cos β (1 − cos β)/R, checked against a search on the solve at 30% for each line, for lines whose resistance is 0.05, 0.1, 0.25, 0.5 and 0.7 of their reactance — the transfer limit over its uncompensated value, against the fraction of the reactance cancelled. Each peaks at k = 1 − √3·R/X, where the impedance angle is 60°: R/X 0.05, ×5.269 at 91.3%; R/X 0.1, ×2.790 at 82.7%; R/X 0.25, ×1.361 at 56.7%; R/X 0.5, ×1.011 at 13.4%; R/X 0.7, no gain at any compensation. A transmission line, with R/X near a tenth, can nearly triple its limit; a distribution feeder near a quarter gains a third; a cable with R/X above 1/√3 = 0.577 is already past sixty degrees and compensation only lowers it.
Fig. 3 The transfer limit over its uncompensated value, against the fraction of reactance cancelled, for lines whose resistance is 0.05, 0.1, 0.25, 0.5 and 0.7 of their reactance. Each peaks at 1−3 R/X1 - \sqrt3\,R/X: five times at 91 per cent for R/X of 0.05, not at all for R/X of 0.7.

A line whose resistance is a twentieth of its reactance — a large overhead transmission line — can have its limit raised 5.27 times, at 91.3 per cent compensation. At a tenth, 2.79 times at 82.7 per cent. The distribution feeder of these essays, at a quarter, gains 1.36 times at 56.7. At a half, the gain is 1.011 — one per cent — at 13.4 per cent compensation. And a line whose resistance exceeds 1/31/\sqrt3, 0.577, of its reactance has an impedance angle already below sixty degrees before any capacitor is fitted: it is past its own best angle, and every series capacitor lowers its limit.

This is the quantitative form of the earlier essay’s observation that series compensation belongs to overhead lines and not to cables. There the argument was about voltage drop and the share of it the reactance makes; here it is about transfer, and the ratio R/XR/X appears again, now as a threshold with an exact value. The 1/(1 − k) of the textbook describes the first line in the figure to within six per cent up to half compensation and overstates it by nearly a third at eighty per cent; it describes the last line not at all.

A worked high-voltage case makes the scale concrete. An overhead line whose resistance is three per cent of its reactance has its optimum at 94.8 per cent compensation, where its limit is 8.59 times the uncompensated one. Compensated to seventy per cent, which is a common figure for such lines, the solve’s closed form gives a gain of 3.08 against the textbook’s 3.33; at half compensation, 1.94 against 2.00. For such a line the lossless formula is a fair tool over the range compensation is actually used in, and it is useful to know that it is fair because the line sits a long way from its sixty degrees, not because resistance does not matter. For a distribution feeder the same formula is wrong at every compensation worth installing.

The angle it buys, and the headroom it does not

A transmission line is not run at its limit. It is run at an angle well below the limit’s, and the difference is the margin against a disturbance pushing the angle over the top. So the other reading of compensation is the angle a fixed transfer needs.

A 100 kW transfer needs 25.2° between the sources uncompensated and 14.6° at half compensation — but the limit angle falls too, from 76.0° to 63.4°. computed by solving, not by drawing, at 50 Hz, bisected: the angle between the two 230 V sources at which the receiving end takes 100 kW (lower curve), and the angle at which it takes the most it can (upper curve), against the fraction of the line's reactance cancelled. 0%: 25.18° of 75.96°; 10%: 22.85° of 74.48°; 20%: 20.61° of 72.65°; 30%: 18.47° of 70.35°; 40%: 16.46° of 67.38°; 50%: 14.63° of 63.43°; 57%: 13.55° of 60.00°; 60%: 13.09° of 57.99°; 70%: 12.18° of 50.19°; 80%: 13.07° of 38.66°. The operating angle falls with the cancellation, and so does the angle of the limit, which is the line's impedance angle; the headroom between them is the quantity a stability margin is written in, and it does not grow with the compensation.
Fig. 4 The angle between the sources at which the receiving end takes 100 kW (lower curve), and the angle at which it takes the most it can (upper curve), against the fraction cancelled, bisected on the solve. At half compensation 100 kW needs 14.6° against 25.2° uncompensated — and the limit’s angle has fallen from 76.0° to 63.4°.

A 100 kW transfer needs 25.2° uncompensated, 18.5° at 30 per cent and 14.6° at half: the capacitor lets the same power pass at a smaller angle, which is what it is sold for. But the limit’s angle is the line’s impedance angle, and the capacitor lowers that too, from 76.0° to 63.4° at half compensation and to 50.2° at 70 per cent. The headroom between operating angle and limit angle is 50.8° uncompensated, 48.8° at half compensation and 38.0° at 70 per cent: nearly constant at first, and then shrinking, because past the peak the operating angle stops falling — at 80 per cent 100 kW needs 13.1°, more than the 12.2° it needed at 70 — while the limit’s angle keeps falling.

So the margin argument and the power argument part company. By the lossless reasoning, compensation always helps both: smaller operating angle, same 90° limit angle, more headroom. With resistance, the limit’s angle moves down with the compensation, and the headroom in degrees is roughly conserved until the peak and lost after it. A designer reading the operating angle alone would conclude that more compensation is always safer; the solve says the extra safety is spent as it is bought.

The shape is familiar from a different limit in these essays. The load that has two voltages or none found a fixed-power load on a line delivered at two voltages below a limit and at none above it, the limit sitting at the load the maximum-power theorem picks. The angle between two sources is the same kind of variable: every power below the limit is carried at two angles, one on each side of the impedance angle, and only the smaller is a stable operating point, because on the far side a larger angle carries less power and a disturbance that opens the angle is not opposed. Compensation moves the top of that curve up and to the left at once, and the headroom between the operating point and the top is what a stability margin measures.

A control that responds to a shortfall by opening the angle further — a governor asked for more power — is stable only on the near side of the peak, for the reason the regulator that pushes past the nose found for a tap changer that raises its ratio whenever the voltage is low: past the peak, the action that used to raise the quantity lowers it, and the loop that was correcting now runs away. Compensation does not change that structure. It moves the peak, and past the optimum it moves it the wrong way, to a lower power at a smaller angle, which is the least comfortable place for a peak to be when the controller does not know where it is.

Half of what is sent

The last reading is the one that turns a transmission-line result into an old friend.

At its own limit the line delivers 67.3% of what it is sent uncompensated, and exactly 50% at the compensation that makes that limit largest. computed by solving, not by drawing, at 50 Hz, at the angle of the largest received power for each compensation: the received power over the sent power on the 230 V tie of 0.05 + j0.2 Ω. It is 1/(1 + 2 cos β) for an impedance angle β — 67.34% uncompensated, 50.0000% at 56.7% cancellation, where β = 60°, and falling towards a third as the line is cancelled towards a resistance. The largest transfer is bought by operating the line exactly where it wastes as much as it delivers: the maximum power theorem, reached by the angle between two sources instead of by a load resistance.
Fig. 5 The received power over the sent power, at the angle of the largest received power, against the fraction of the reactance cancelled. It is 1/(1 + 2 cos β): 67.3 per cent uncompensated, exactly 50 per cent at 56.7 per cent cancellation, and falling towards a third.

At the angle of its largest delivery, a line delivers a fraction of what it is sent that depends only on its impedance angle: the sent power at δ=β\delta = \beta is V2cos⁡β(cos⁡β−cos⁡2β)/RV^2\cos\beta(\cos\beta - \cos2\beta)/R, and the ratio of received to sent is 1/(1+2cos⁡β)1/(1 + 2\cos\beta). Uncompensated, with cos⁡β=0.2425\cos\beta = 0.2425, the line at its limit delivers 67.3 per cent of what goes in. At the compensation that makes the limit largest, cos⁡β=12\cos\beta = \tfrac12, it delivers exactly 50 per cent — the solve gives 50.0000 — and as the line is cancelled towards a pure resistance the fraction falls towards a third.

Half is not a coincidence. The load that takes the most found a load resistance equal to its source’s taking more power than any other, at exactly fifty per cent efficiency, with the source burning as much as the load receives. Here there is no load resistance to choose: the receiving end is a source, and what is chosen is the angle and the compensation. The two together play the same role, and the largest power that can be delivered is delivered, as always, with as much again lost on the way. The load that may be complex reached the conjugate match by cancelling reactance with an opposite one; series compensation is that cancellation made in the line instead of at the load, and it stops short of full cancellation for the reason the maximum-power theorem gives — the best transfer is at a sixty-degree line, not a zero-degree one, because the receiving source’s voltage is fixed and cannot be matched the way a load resistance can.

How the numbers were obtained

Every figure solves one netlist at 50 Hz: a 230 V source at an angle δ\delta, the line’s resistance and inductance, a series capacitor sized to cancel the stated fraction of the reactance, and a 230 V source at zero phase at the far end. The line current is read from the voltage across the resistance, and the received and sent powers are the real parts of each source’s voltage times the conjugate of that current. The largest received power is found by golden-section search over δ\delta from zero to 180 degrees on the solve, and is compared with V2cos⁡β(1−cos⁡β)/RV^2\cos\beta(1 - \cos\beta)/R, never replaced by it; the angle for 100 kW is bisected on the solve. The ratio figure evaluates the closed form and checks it against the search at 30 per cent compensation on every line.

What it leaves out

The machines at the two ends. Both ends are ideal sources. A real transfer limit is set by generators whose internal reactance adds to the line’s, which raises the impedance angle and moves the optimum compensation higher; and the dynamic limit — whether the angle recovers after a fault — depends on their inertia, which this solve does not have.

Unequal voltages. Both sources are at 230 V. With the receiving end lower, the closed form gains a term in the product of the two magnitudes and the peak moves; the sixty-degree result is for equal magnitudes, which is the condition a transmission system is operated near.

The resonance. A compensated line has the sub-synchronous resonance the reactance cancelled, and the resonance it buys found at f0kf_0\sqrt k — 37.6 Hz at the optimum here — and a generator’s shaft has torsional modes at such frequencies. That interaction, not the steady-state limit, is what usually caps compensation on a real line well below the peak this essay finds.

Still open: the machines’ reactance, unequal ends, and the capacitor’s own losses

The generator’s reactance in the loop. Adding each machine’s internal reactance to the line’s raises the total impedance angle, which moves k∗k^* up — the capacitor then cancels a fraction of a larger reactance of which it can reach only the line’s part. Whether the sixty-degree optimum survives when part of the reactance is out of reach is a solve with two more inductors in it.

A capacitor with losses. The reactance that is not free found a cancelling capacitor’s own resistance, its reactance over its Q, eating into what cancellation buys. Here that resistance adds to the line’s and so raises R/XR/X as kk rises — pushing the peak to a lower compensation, and for a poor enough capacitor abolishing it. How good a capacitor has to be for the peak to stay near 1−3R/X1 - \sqrt3 R/X is a small closed form this essay did not write down.

Unequal ends and a load in the middle. With the receiving voltage below the sending, and with load tapped along the tie, the transfer limit becomes a surface over two voltages and a position, and the compensation that maximises it is no longer a single number.

Part 3 on series compensation

One argument about Series compensation, and one of 5 essays on it so far, each part numbered by how much of the idea it assumes. What sits either side of it:

Cancelling 50% of the line's reactance: a 0.3 lagging load's regulation goes from 7.78% to 4.18%, a unity one's from 2.17% to 1.96%, a 0.7 leading one's from −3.78% to −1.26%. computed by solving, not by drawing, at 50 Hz: a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, its regulation against the load's power factor from 0.7 leading to 0.3 lagging, with no compensation (dashed) and with 50% of the line's reactance cancelled by a series capacitor (solid). The solve agrees with the voltage divider in closed form to 9e-10 of a per cent. At 0.3 lagging the regulation falls from 7.781% to 4.176%; at 0.9 lagging, from 5.168% to 3.381%; at unity, only from 2.171% to 1.960%; and at 0.7 leading the far end, above the source at −3.778%, comes down to −1.255%. The capacitor cancels what the load's reactive current does in the line's reactance, in either direction, and pulls every load towards the regulation the line's resistance alone would give. The drop a series capacitor can reach Part 2 — A series capacitor cancels part of a line's reactance, so it can only cancel the part of the drop that the reactance makes — and that part is set by the load, not the line. On a 230 V feeder of 0.05 + j0.2 Ω carrying 20 kVA, half compensation takes a 0.3 lagging load from 7.78% regulation to 4.18% and a unity load only from 2.17% to 1.96%, and it brings a 0.71 leading load's raised far end back down. Cancel all of it and a leading load and its lagging twin sit at exactly the same voltage. Cancel more and the far end rises with its load; at exactly 100% the resonance is the fundamental and a far-end fault draws 4,600 A. Where the capacitor goes, the load cannot tell. With 0.05 Ω of machine reactance at each end the sixty-degree peak needs 107% of the line cancelled — out of reach — so the limit rises all the way to full cancellation, 261.6 kW against 145.3. computed by solving, not by drawing, at 50 Hz, searched over the angle between the two EMFs on the solve (dots) and from V²·cos β·(1 − cos β)/R with the totals in it (line): the 230 V tie of 0.05 + j0.2 Ω with each source a machine whose EMF is held behind 0.05 Ω of its own reactance, against the fraction of the LINE's reactance cancelled. The capacitor cannot reach the machines' reactance, so the total impedance angle reaches sixty degrees only at k* = (X + 2Xₘ − √3·R)/X = 106.7%, beyond full cancellation; the limit rises from 145.34 to 261.55 kW and never turns. Dashed: the bare tie, peaking at 56.7%. The slider is the machines' reactance. The reactance the capacitor cannot reach Part 4 — A series capacitor raises a tie's transfer limit until the loop's impedance angle is sixty degrees, and on a bare 0.05 + j0.2 Ω line that is 56.7% cancellation. Put a machine at each end, its EMF held behind a reactance of its own, and the capacitor still cancels only the line: the sixty degrees now needs the line's reactance plus twice a machine's, less √3 times the resistance, as a fraction of the line's reactance, which passes 100% as soon as each machine's reactance exceeds √3/2 of the line's resistance — 0.043 Ω here. Beyond that the limit rises at every step to full cancellation, and the lossless estimate of the gain, wildly high on a bare line, becomes nearly right: 1.43 against 1.50 at 0.2 Ω. The higher limit is reached with the receiving terminal lower — 180 V falling to 148 at 0.1 Ω — and the capacitor's own resistance is negligible for any power capacitor: a Q of 222 keeps the peak within 1%.