Transformer — where it appears
Named by 17 essays across 5 fields — each of them below, with the objects they name alongside it.
The band a turns ratio holds over
Most circuit models are right below a number or above one. A transformer is wrong at both ends and right in the middle, and the flat part is not the turns ratio either — measured on the solve it is the turns ratio times the coupling, times what the two winding resistances leave of the whole loop — and the first version of that last factor was a coincidence that held for every coupling and broke at a different load.
What coupling buys, and where it does not
Winding a transformer better is winding it more tightly coupled, and the coupling coefficient is the number a maker works on. Measured across six designs from k = 0.8 to k = 0.999, it moves the upper band edge by 168 times and the lower one by 1.083 — so every hour spent on the winding buys bandwidth at one end of the band and, to within eight per cent, nothing at all at the other.
Which picture sets the upper edge
Every account of a transformer's high-frequency limit names the same mechanism: the leakage inductance resonating with the winding capacitance. At fifty ohms that resonance is at 1.13 MHz and the measured edge is at 81.3 kHz — a factor of fourteen away — because what actually binds is the leakage in series with the load, a first-order corner with no resonance in it at all. The two swap at about 1500 Ω, and both accounts are current because both are sometimes right.
Where the band goes entirely
The three essays before this one measure a transformer's band, and all three assume there is one. Past a few hundred ohms of load there is not: the leakage that sets the upper edge is also what damps the resonance behind it, and a lightly loaded, well-coupled transformer peaks at 3.03 times its own turns ratio. A passive component with voltage gain is not a transformer behaving badly. It is a resonant circuit, and asking for its band returns the skirts of a resonance.
One number from two measurements
Neither of the two standing checks on a solved circuit can see a mutual inductance. A coupling adds no current anywhere, so Kirchhoff's law is unmoved by it; a coupled pair dissipates nothing, so the energy balance is unmoved too. A coupling stamped into the wrong row would produce a well-formed solution to a different circuit and both checks would pass — so the field needed a third route, and the one it uses is the bench method: connect the windings in series one way, then the other, and the difference is four times the mutual inductance.
Two ports from two one-ports
An inductor is a one-port: one impedance, one number. Two of them coupled is a two-port, and the four impedance parameters that describe it are recovered here by four solves — each port driven with the other open, the definition read literally. Two of the four come out equal to 2.8 × 10⁻¹⁶, which is reciprocity, and is the first property a coupling stamped into one row instead of two would break.
The copper that makes it worse
The rung below measured one conductor pushing its own current to its rim, and there is nothing to optimise in it: thicker wire is always less resistance. Stack the conductors and the quantity changes character. Each layer sits in the field of the ones below it, the loss that field drives has no upper bound in the thickness, and the product turns over — so a portion of four layers has a best foil thickness, and above it more copper is more resistance. The best thickness is the fourth root of three over the square root of the layer count, in skin depths, and the penalty at it is four thirds for every layer count above one.
The current that sizes the transformer
A reservoir's crest factor is 13.374 at a thousand microfarads and the winding is not sized by it. The root-mean-square of the same marched current is 3.0069 times the load's direct current, so the copper dissipates 9.0417 times what it would carrying the direct current alone — and the two ratios diverge, from 3.04 apart at 220 microfarads to 5.95 apart at 4700. The expression for the mean output is wrong in three places whose signs differ, and at 313.9 microfarads they cancel to six microvolts while the ripple expression inside it is still 32.3 per cent high.
The resistance that belongs in the winding
A reservoir capacitor's series resistance lowers the ripple to a minimum of 1.3303 V at 17 mΩ and raises it past that. The same resistance moved into the transformer's winding limits the peak current by the same amount — the crest factor agrees to two parts in a thousand at every value from a milliohm to an ohm — and the minimum is gone: the ripple falls throughout, to 1.172 V at an ohm against 1.711 V in the capacitor. The two resistances each carry a current the other does not, and that one asymmetry decides where a deliberate one should go.
The inductance that is a shape
Leakage inductance is the one transformer parameter that belongs to the geometry rather than to the material: twice the magnetic energy in the window under equal and opposite ampere-turns, divided by the square of the current. Solved as a field it is 3.086 microhenries a metre against a closed form's 3.128 when the copper fills the window, and 4.608 against 6.255 when it fills half of it. Interleaving is worth 3.11 times and not the four it is quoted as, and the missing 0.89 is the insulation nobody puts in the formula.
The ring a blocking capacitor buys
A series capacitor in front of a transformer stops its flux from walking: a 55%-duty drive that walks a bare core by 0.40 units of volt-time a period settles within a few dozen periods once the capacitor takes the drive's average. The price is a second-order high-pass with the magnetising inductance, and an inductance lets its poles go complex where two resistive coupling stages never could. Between equal resistances the damping cannot fall below 1/√2, and the poles are complex only for a capacitor between 0.17 and 5.8 times L/R². From a stiff driver the damping is √(L/C)/2R and has no floor: a capacitor large enough to make the droop small — the droop is 1/RC, the capacitor's and not the transformer's — makes the tail ring, from one zero crossing at a tenth of L/R² to thirty-five at a hundred.
One turns ratio for a band
A 50 Ω source and an amplifier whose optimum is 6.67 kΩ want a step-up transformer, and the ratio that matches the white optimum, 11.5, is the one a design note computes. Over the audio band it is nearly right: 1.31 dB against 1.30 at the band's own best ratio, 10.7. Over 1 Hz to 100 Hz it is badly wrong — 9.2 dB where a ratio of 4.8 gives 5.4 — because the band's noise lives in its bottom decade, where the flicker has moved the optimum down. One ratio for a two-decade band costs at most 0.24 dB against a ratio that could follow the optimum. The transformer's winding resistance multiplies the whole noise factor by one plus the winding's resistance over the source's, not just its own share: a tenth of the source costs 0.41 dB where its own noise alone would cost 0.31. And 115 amplifiers in parallel are an ideal 10.7:1 transformer, noise for noise.
The leakage a series reading cannot see
The series-aiding and series-opposing readings recover a coupling coefficient to fifteen figures on a netlist, and on a bench with a 0.1% meter they recover it to about 0.001 at every coupling — which is useless exactly where transformers live. At k = 0.999 the leakage, L₁(1 − k²), is two thousandths of the winding, and the series route leaves it 133% uncertain: 88 of 400 seeded benches report a negative leakage. Shorting the other winding reads the leakage directly, to the meter's own 0.1%, and recovers k 943 times more precisely at 0.999. The short is a short only where the shorted winding's reactance dwarfs its resistance by 10k/√(1 − k²), and the winding to short is the one with the longer time constant.
The instant a transformer is worst at
A capacitor-input rectifier draws its worst inrush when it is switched on at the peak of the mains. A transformer's own magnetising branch is the other way round: switched on at the voltage zero, a 230 V primary worked at 1.4 T draws 87.6 A in its first half-cycle, 791 times its settled magnetising current, and at the voltage peak it draws nothing extra at all. The core's flux has to start from zero, the voltage does not, and how close the working flux sits to half of saturation decides the size.
The band counted in rise times
A transformer's band is two frequencies and its pulse response is two times, and they are the same two facts. Through the 1:1, k = 0.99 transformer whose band runs 400 Hz to 81.3 kHz, a 100 µs pulse rises in 4.03 µs — 0.35 over the upper band edge — and droops 21.6% along its top with a time constant of one over 2π times the lower edge, 398 µs; solved by residues and by a march of the netlist, they agree to a third of a per cent. Coupling buys rise time and nothing else: from 30.8 µs at k = 0.9 to 422 ns at 0.999, while the droop's time constant moves from 414 to 396 µs. The longest pulse that droops no more than 10%, over the rise, is 0.048 times the ratio of the upper band edge to the lower — the band ratio counted in rise times, 10.4 at k = 0.99 and 98.8 at 0.999. And the droop is not lost: a transformer has no gain at direct current, so the output swings below zero afterwards by exactly what the top lost, and the two areas match to 0.08%.
The resistors that sum a hundred amplifiers
A hundred amplifiers in parallel across a 50 Ω source are an ideal transformer of ratio ten, and the summing network between them and the output is where the comparison was left. Its resistors turn out to be the least of it. N resistors averaging N outputs make the noise of R/N, falling exactly as the amplifiers' voltage noise does, so the resistor equal to a 4 nV/√Hz amplifier is about a kilohm at every N, and at 133 parts 200 Ω costs only a tenth of a decibel. The stage that was forgotten is whatever reads the sum. Averaging leaves it alone, so a following amplifier as good as one of the parts costs 12.14 dB, and each part needs a gain of 26 to bring that under a tenth. Parallel amplifiers then match a transformer with one ohm of winding.
The window that moves
A shorted winding reads its own leakage only above the frequency at which the short really cancels the shared flux, and only below the leakage's resonance with whatever capacitance is across it. A tighter coupling raises the first edge as one over the root of 1 − k², and it was expected to pull the second down and close the window. It raises the second as well, by the same factor. So the band is 82 Hz to 36 kHz at k = 0.9, 279 Hz to 112 kHz at 0.99 and 2.81 kHz to 1.12 MHz at 0.9999, about four hundred times wide throughout. Its width is 0.01·L₂/(R₂k√(L₁C)), with the leakage nowhere in it, so what closes the window is the winding and not the coupling. Reading the real part as well is exact on paper and limited by phase.
Named alongside it
The objects these essays reach for when they reach for this one.
Leakage inductanceCoupling coefficientDesign tradeoffMagnetising inductanceMutual inductanceClosed formWindingBandwidthConduction angleCrest factorInterleavingInterwinding capacitance